Plan Review Notes
Plan Review Notes For Permit 17040244
Permit Number 17040244
Review Stop P
Sequence Number 2
Notes
Date Text
2017-04-18 04:50:321) THIS DEVICE IS NOT LISTED ON THE USC WEBSITE AS AN
 APPROVED DEVICE AS REQUIRED BY THE CWPB
 CROSS-CONNECTION CONTROL MANUAL AND THEREFORE CANNOT BE
 USED.
 2) SUBMIT A PLAN SHOWING THE LOCATION AN APPROVED
 BACKFLOW PREVENTER. IF THERE IS A SEPARATE METER
 DEDICATED TO THE IRRIGATION SYSTEM, THEN THE MINIMUM
 LEVEL OF PROTECTION SHALL BE A DOUBLE CHECK VALVE
 ASSEMBLY PER THE CWPB CROSS-CONNECTION CONTROL MANUAL.
 3) SUBMIT A DETAIL SHOWING THE ARRANGEMENT OF THE
 BACKFLOW PREVENTER ON THE IRRIGATION SYSTEM. AN
 ATMOSPHERIC BACKFLOW PREVENTER DEVICE IS NOT FOR USE
 UNDER CONTINUOUS PRESSURE SO IT WOULD HAVE TO BE
 LOCATED DOWNSTREAM OF A SOLENOID VALVE ON THE SYSTEM.
 CLARIFY.
 4) THIS DEVICE (288A) IS DESIGNED FOR LOW FLOW WATER
 INSTALLATIONS AND DOES NOT APPEAR TO BE APPROPRIATE FOR
 AN IRRIGATION SYSTEM APPLICATION.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  