| 2017-04-18 04:50:32 | 1) THIS DEVICE IS NOT LISTED ON THE USC WEBSITE AS AN | | | APPROVED DEVICE AS REQUIRED BY THE CWPB | | | CROSS-CONNECTION CONTROL MANUAL AND THEREFORE CANNOT BE | | | USED. | | | 2) SUBMIT A PLAN SHOWING THE LOCATION AN APPROVED | | | BACKFLOW PREVENTER. IF THERE IS A SEPARATE METER | | | DEDICATED TO THE IRRIGATION SYSTEM, THEN THE MINIMUM | | | LEVEL OF PROTECTION SHALL BE A DOUBLE CHECK VALVE | | | ASSEMBLY PER THE CWPB CROSS-CONNECTION CONTROL MANUAL. | | | 3) SUBMIT A DETAIL SHOWING THE ARRANGEMENT OF THE | | | BACKFLOW PREVENTER ON THE IRRIGATION SYSTEM. AN | | | ATMOSPHERIC BACKFLOW PREVENTER DEVICE IS NOT FOR USE | | | UNDER CONTINUOUS PRESSURE SO IT WOULD HAVE TO BE | | | LOCATED DOWNSTREAM OF A SOLENOID VALVE ON THE SYSTEM. | | | CLARIFY. | | | 4) THIS DEVICE (288A) IS DESIGNED FOR LOW FLOW WATER | | | INSTALLATIONS AND DOES NOT APPEAR TO BE APPROPRIATE FOR | | | AN IRRIGATION SYSTEM APPLICATION. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|