Plan Review Notes
Plan Review Notes For Permit 17040244
Permit Number 17040244
Review Stop P
Sequence Number 1
Notes
Date Text
2017-04-07 16:48:211ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. DEVICE IS NOT LEAD FREE AND CAN NOT BE USED IN
 CONNECTION OF POTABLE WATER SYSTEMS. PER FBC PL 605.2.1
  
 2. DEVICES SHALL BE APPROVED FOR LEAD FREE ON THE
 UNIVERSITY OF SOUTHERN CALIFORNIA'S LIST OF APPROVED
 DEVICES. PER WPB UTILITIES CROSS CONNECTION CONTROL
 MANUAL
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  