| 2017-04-25 10:02:38 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS. |
| | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| | THE CENTERLINE OF THE DISPENSER. |
| | |
| | 2. GRAB BARS ARE TO BE MEASURED FROM THE TOP OF THE |
| | GRIPPING SURFACE TO FINISHED FLOOR NOT THE CENTER OF |
| | THE BAR. PER FBC ACC 609.4 |
| | |
| | 3.THE BREAK ROOM SINK AND AT LEAST ONE OF THE TREATMENT |
| | ROOM SINKS SHALL COMPLY WITH FBC ACC 606.2 CLEAR FLOOR |
| | SPACE. |
| | A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR |
| | A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE |
| | COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 4. THE SHOWER SHALL COMPLY WITH ONE OF THE SHOWER TYPES |
| | IN FBC ACC 608 PROVIDE DIMENSIONS AND MOUNTING HEIGHTS |
| | ON THE PLAN. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. THE BRANCH DRAIN FOR THE TREATMENT ROOM SINKS AND |
| | BREAK ROOM SINK SHALL CONNECT TO THE BUILDING DRAIN |
| | DOWN STREAM OF THE BATHROOM GROUP. PER FBC PL 912.1 |
| | |
| | 6. THE LAVATORY IN THE BATHROOM SHALL COMPLY WITH FBC |
| | PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING |
| | FACILITIES. |
| | TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND |
| | GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES |
| | PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED |
| | WATER SHALL BE DELIVERED THROUGH AN APPROVED |
| | WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| | 1070 OR CSA B125.3. |
| | 607.1.1 TEMPERATURE LIMITING MEANS. |
| | A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE |
| | AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF |
| | COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR |
| | MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY |
| | TEMPERATURE AT FIXTURES. |
| | |
| | |
| | |
| | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT |
| | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL |
| | COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |