Plan Review Notes
Plan Review Notes For Permit 17040239
Permit Number 17040239
Review Stop P
Sequence Number 1
Notes
Date Text
2017-04-25 10:02:381ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW COMPLIANCE WITH FBC ACC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 2. GRAB BARS ARE TO BE MEASURED FROM THE TOP OF THE
 GRIPPING SURFACE TO FINISHED FLOOR NOT THE CENTER OF
 THE BAR. PER FBC ACC 609.4
  
 3.THE BREAK ROOM SINK AND AT LEAST ONE OF THE TREATMENT
 ROOM SINKS SHALL COMPLY WITH FBC ACC 606.2 CLEAR FLOOR
 SPACE.
 A CLEAR FLOOR SPACE COMPLYING WITH 305, POSITIONED FOR
 A FORWARD APPROACH, AND KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4. THE SHOWER SHALL COMPLY WITH ONE OF THE SHOWER TYPES
 IN FBC ACC 608 PROVIDE DIMENSIONS AND MOUNTING HEIGHTS
 ON THE PLAN. PER WPB AMEND TO FBC 107.2.1
  
 5. THE BRANCH DRAIN FOR THE TREATMENT ROOM SINKS AND
 BREAK ROOM SINK SHALL CONNECT TO THE BUILDING DRAIN
 DOWN STREAM OF THE BATHROOM GROUP. PER FBC PL 912.1
  
 6. THE LAVATORY IN THE BATHROOM SHALL COMPLY WITH FBC
 PL 416.5 TEMPERED WATER FOR PUBLIC HAND-WASHING
 FACILITIES.
 TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES AND
 GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET FACILITIES
 PROVIDED FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED
 WATER SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 607.1.1 TEMPERATURE LIMITING MEANS.
 A THERMOSTAT CONTROL FOR A WATER HEATER SHALL NOT SERVE
 AS THE TEMPERATURE LIMITING MEANS FOR THE PURPOSES OF
 COMPLYING WITH THE REQUIREMENTS OF THIS CODE FOR
 MAXIMUM ALLOWABLE HOT OR TEMPERED WATER DELIVERY
 TEMPERATURE AT FIXTURES.
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  