Plan Review Notes For Permit 17040239
Permit Number 17040239
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-12 15:08:011ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING CODES
 PERMIT #17040239
 4/12/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) REFER TO SECTION C403.2.7.5 FBC-14 ENERGY
 CONSERVATION AND INDICATE HOW THE AIR DISTRIBUTION
 SYSTEM WAS SIZED AND DESIGNED.
  
 3) A MEANS OF RETURN AIR OTHER THAN UNDERCUTTING DOORS
 IS REQUIRED FOR THE TREATMENT ROOMS AND THE OFFICE- SEE
 SECTION 601.5
  
 4) THE SPA SERVICES NOTES ON SHEET A-01 INDICATES
 MANICURES WILL BE PERFORMED. PLEASE SHOW THE LOCATIONS
 OF THE NAIL STATIONS AND PROVIDE EXHAUST SYSTEMS IN
 COMPLIANCE WITH TABLE 403.3 .
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER