Plan Review Notes
Plan Review Notes For Permit 17040239
Permit Number 17040239
Review Stop E
Sequence Number 1
Notes
Date Text
2017-04-21 08:32:36INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO CCTV,
 PHONE AND DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL
 SUFFICE.
 2. PLEASE LABEL ALL RECEPTACLES WITHIN 6FT OF ALL
 SINKS, SEE MULTIPLE LOCATIONS. NEC 210.8B
 3. ADD RECEPTACLE FOR AC ON ROOFTOP WITHIN 25FT OF
 UNIT, SHOW IF EXISTING. FBC 107.3.5
 4. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  