Plan Review Notes
Plan Review Notes For Permit 17040239
Permit Number 17040239
Review Stop B
Sequence Number 1
Notes
Date Text
2017-04-14 16:00:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. ACCESSIBLE ROUTE TO THE ALTERED AREA IS REQUIRED,
 FBC A 202.4. THE ENTRY DOOR DOES NOT MEET THE
 REQUIREMENTS OF FBC A 303.
  
 2. FBC 109, PROVIDE A COPY OF THE CONTRACT FOR THIS
 JOB. ADDITIONAL INFORMATION MAY BE REQUIRED.
  
 3. A01 RESTROOM DETAILS INCLUDE OUTDATED REFERENCES (CH
 11) AND DETAIL NOT COMPLIANT, SEE GRAB BAR HEIGHT
 REQUIREMENT TO BE MEASURED TO TOP OF BAR, FBC A 609.4.
 CHECK ALL DETAILS.
  