| Date |
Text |
| 2017-04-11 16:51:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) |
| | SHEET A 0.01 - THERE INCORRECT REFERENCES INDICATED FOR |
| | THE CURRENT EDITIONS OF THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 10, 2010 EDITION. |
| | ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2011 EDITION. |
| | EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH |
| | NFPA 110, 2013 EDITION. |
| | AIR CONDITION WORK SHALL COMPLY WITH NFPA 90 A & B, |
| | 2012 EDITION |
| | |
| | PLEASE CORRECT ALL THE APPLICABLE CODE EDITIONS. |
| | |
| | |
| | |
| | 2) |
| | SHEETS A 0.0. & 0.03 - NOTE # 7 MAKES REFERENCE TO AND |
| | INCORRECT NFPA 13 EDITION. |
| | |
| | PLEASE CORRECT AS NOTED ON # 1 ABOVE. |
| | |
| | |
| | |
| | |
| | 3) |
| | SHEET A 1.11 - THERE ARE INDICATIONS OF WALL TYPE |
| | REFERENCE OF A BOX AROUND, S1, TO WALLS CONTAINING FIRE |
| | RATED DOORS. ON SHEETS A 5.11 & 5.12 THERE ARE NO |
| | INDICATORS MATHCING THAT REFERENCE OR ANY OTHER LISTED |
| | WALL RATING. |
| | |
| | PLEASE PROVIDE THE APPLICABLE LISTED WALL RATING FOR |
| | THAT REFERENCE. |
| | |
| | |
| | |
| | |
| | 4) |
| | SHEET A 0.02 & 0.03 - NOTE # 4 INDICATES REFERNCES TO |
| | LIFE SAFETY DEVICES ON THE ELECTICAL SHEETS. THERE ARE |
| | NO INDICATORS OF ANY FIRE ALARM DEVICES ON ANY |
| | ELECTICAL SHEET. |
| | |
| | ANY AND ALL WORK ON THE FIRE ALARM SYSTEM SHALL BE DONE |
| | UNDER SEPARATE SHOP DRAWINGS AND BY CERTIFIED LIFE |
| | SAFETY CONTRACTORS. |
| | |
| | THE FIRE ALARM SYSTEM SHALL REMAIN ACTIVE THROUGHOUT |
| | THE CONSTRUCTION PERIOD. |
| | |
| | PLEASE PROVIDE AN APLLICABLE NOTE. |
| | |
| | |
| | |
| | 5) |
| | SHEET E - THE ELECTRICAL SHEETS INDICATE CARD READERS |
| | ON EXIT DOORS. THESE CARD READERS SHALL DELAY OR |
| | INTERFERE WITH ANY EXIT DOOR AND SHALL COMPLY WITH NFPA |
| | 101, CHAPTER 7, MEANS OF EGRESS AND SHALL BE INSTALLED |
| | UNDER SEPARATE SHOP DRAWINGS. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE. |
| | |
| | |
| | |
| | 6) |
| | SHEET A 0.01 - NOTE # 7 REFERENCES WORK ON THE FIRE |
| | SPRINKLER SYSTEMS. THE FIRE SPRINKLER SHALL REMAIN |
| | ACTIVE THROUGHOUT THE CONSTRUCTION PERIOD. ANY TIME |
| | THAT WORK ON THE FIRE SPRINKLER SYSTEM EXCEEDS 4 HOURS, |
| | A FIRE WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL |
| | FULL AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | PLEASE PROVIDE AND APPLICABLE NOTE. |
| | |
| | |
| | 7) |
| | SHEET A 0.02 & 0.03 - FOR INFORMATIONAL PURPOSES, THERE |
| | IS A MISSPELLED WORD; "OCCUYPANCY", INDICATED IN THE |
| | TABLE HEADER. |
| | |
| | |
| | |
| | 8) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 9) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |