| Plan Review Notes For Permit 17040185 |
| Permit Number |
17040185 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-01-09 08:46:41 | 1) THE SUBMITTED NARRATIVE CALLS OUT SPECIFIC CHANGES | | | TO THE PLUMBING DRAWINGS BUT NOT ALL OF THE CHANGES | | | NOTED IN THE NARRATIVE ARE CLOUDED/IDENTIFIED ON THE | | | REVISED PLUMBING DRAWINGS. CLEARLY IDENTIFY ALL THE | | | CHANGES TO THE PLUMBING SYSTEM ON THE REVISED DRAWINGS | | | TO CORRELATE WITH THE CHANGES SPECIFIED IN THE | | | NARRATIVE. WPB AMEND. TO FBC SEC. 107.2.1. | | | 2) SUBMIT THE MANUFACTURER'S | | | SPECIFICATIONS/INSTALLATION REQUIREMENTS FOR THE | | | FLEXIBLE COUPLINGS INSTALLED IN THE SANITARY SYSTEM AS | | | REFERENCED IN THE NARRATIVE. COUPLINGS SHALL COMPLY | | | WITH THE FBC-PLUMBING SEC. 705. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|