Plan Review Notes
Plan Review Notes For Permit 17040185
Permit Number 17040185
Review Stop M
Sequence Number 2
Notes
Date Text
2017-12-20 12:15:332ND REVIEW FBC-2014 MECHANICAL
 PERMIT #17040185
 12/20/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.118: NOTE #19 APPEARS TO INDICATE TRANSFER
 DUCTS PROVIDING MAKEUP AIR FROM THE CORRIDOR FOR THE
 EXHAUST SYSTEMS. PLEASE SEE SECTION 601.2 EXCEPTION 1
 WHICH PERMITS THE TRANSFERS ONLY IF OUTDOOR AIR IS
 BEING SUPPLIED TO THE ROOMS AT A RATE GREATER THAN THAT
 OF THE MAKEUP AIR.
  