2017-04-27 11:27:521) SHT.A2.312 - THE NARRATIVE REFERS TO ADDED BACKWATER
 VALVES ON STORM DRAINS. CLOUD THE AREAS OF THE CHANGE
 ON THE PLANS. WPB AMEND. TO FBC SEC. 107.2.1.
 2) SHT. A3.03 - THE NARRATIVE REFERS TO SANITARY RISER
 SAN-11 AND AREA DRAINS BUT THE DRAWING IS FOR GYPSUM
 BOARD DETAILS. CLARIFY.
 3) SHT. A3.54 - THE NARRRATIVE REFERS TO BACKWATER
 VALVES ON THE STORM DRAINS BUT THE DRAWING IS FOR
 CASEWORK DETAILS/ELEVATIONS. CLARIFY.
 4) PLUMBING SHEETS - PLEASE PUT THE ROOM NUMBERS ON THE
 PLANS. THIS WILL HELP WITH THE REVIEW PROCESS.ALSO,
 CLOUD ALL THE CHANGES ON THE PLUMBING DRAWINGS.WPB
 AMEND. TO FBC SEC. 107.2.1.
 5) SHT. P2.108 - THE NARRATIVE NOTES "COORDINATION WITH
 HYDROTHERAPY POOL DESIGN." CLARIFY. WHAT WAS REVISED?
 BE SPECIFIC AS TO THE CHANGE(S) THAT HAVE BEEN MADE.
 SEE NARRATIVE FOR SHT. P.111 ALSO.
 6) THERE ARE NUMEROUS PLUMBING SHEETS WHERE THE
 NARRATIVE NOTES CHANGES TO THE PLUMBING SYSTEM BUT
 THESE CHANGES ARE NOT CLEARLY IDENTIFIED ON THE PLANS.
 IDENTIFY THE CHANGES TO THE PLUMBING SYSTEM BY
 CLOUDING. SHEETS P2.110, P2.111, P2.112, P2.113,
 P2.118, ETC.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW