Plan Review Notes
Plan Review Notes For Permit 17040185
Permit Number 17040185
Review Stop M
Sequence Number 1
Notes
Date Text
2017-05-24 16:45:561ST REVIEW FBC-2014 MECHANICAL
 REVISION #17040185
 BALLPARK OF THE PALM BEACHES
 PERMIT #S
  
 RESULTS: DENIED.
  
 1) SHEET M2.118. A) NOTE #14: PROVIDE EXHAUST FAN
 EQUIPMENT SCHEDULES AND EXHAUST VENTILATION
 CALCULATIONS. B) NOTES #15, 16, 17, 18, 19: PROVIDE
 SHOP DRAWINGS AND PRODUCT SUBMITTALS FOR THE EXHAUST
 AND TRANSFER DUCTWORK AND FITTINGS APPROVAL SIGNATURES
 BY THE ENGINEER OF RECORD- REFER TO SECTION 510.8 AND
 TABLE 510.8 FBC-14 MECHANICAL FOR REQUIRED TYPE AND
 THICKNESS
  
 OF GALVANIZED DUCT MATERIAL. C) REFER TO SECTION
 414.1.3 FBC-14 BUILDING AND INDICATE THE MAXIMUM
 QUANTITIES OF ACID AND POOL CHEMICALS TO BE STORED IN
 THE EQUIPMENT AND STORAGE ROOMS AND SUBMIT MSDS SHEETS
 FOR THE MATERIALS. D) PROVIDE A SEQUENCE OF OPERATION
 FOR THE EXHAUST FANS.
  
 2) M2.128: PROVIDE WIND LOAD ENGINEERING FOR
 INSTALLATION OF THE ROOFTOP GRAVITY INTAKE AND EXHAUST
 HOODS- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER