2017-04-26 06:39:14****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. A "FACE CHANGE" IS AN INSERT INTO A METAL CABINET
 WITH NO FASTENERS. THIS APPEARS TO BE A CONCRETE OR
 CONCRETE BLOCK MONUMENT WITH A SIGN MOUNTED TO IT.
 REVISE PLAN TO CLARIFY INSTALLATION. IF THIS IS A FACE
 CHANGE, PROVIDE ADDITIONAL PHOTOGRAPHS TO CLARIFY THAT
 THIS DOES INSTALLATION DOES NOT REQUIRE FASTENERS. IF
 THIS DOES REQUIRE FASTENERS, PROVIDE ENGINEERING TO
 SHOW PROPOSED INSTALLATION METHOD, WIND DESIGN
 CRITERIA, FBC B 1609.