2017-04-17 09:11:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY ELECTRICAL
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE ELECTRIC HEAT PUMP POOL HEATER.
 FBC 107.2.1.3
  
 2) SUBMIT TWO SETS OF ELECTRICAL LOAD CALCULATIONS TO
 SHOW THAT THE EXISTING SERVICE IS ADEQUATE FOR THE NEW
 POOL EQUIPMENT. FBCR-E3401.4
  
 3) A POOL ELECTRIC SUB-PERMIT IS REQUIRED TO BE APPLIED
 FOR BEFORE THE POOL PERMIT WILL BE ISSUED. FBC105.1
  