| Plan Review Notes For Permit 17040045 |
| Permit Number |
17040045 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-10 14:06:15 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17040045 | | | 4/10/17 | | | | | | 1) SHEET M0.1: THE OUTSIDE AIR CFMS SHOWN IN THE | | | EQUIPMENT SCHEDULE APPEAR TO BE INADEQUATE. PLEASE | | | REFER TO TABLE 403.3 AND PROVIDE VENTILATION | | | CALCULATIONS FOR ALL ROOMS AND SPACES. PROVIDE A | | | SCHEDULE THAT INCLUDES THE REQUIRED AND PROVIDED O/A | | | AIR. | | | | | | 2) CLARIFY HOW THE WAREHOUSE IS BEING VENTILATED. IS | | | THERE AN EXISTING SYSTEM, OR WILLL A NEW SYSTEM BE | | | PROVIDED- SECTION 401.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|