2017-04-10 14:06:151ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17040045
 4/10/17
  
 1) SHEET M0.1: THE OUTSIDE AIR CFMS SHOWN IN THE
 EQUIPMENT SCHEDULE APPEAR TO BE INADEQUATE. PLEASE
 REFER TO TABLE 403.3 AND PROVIDE VENTILATION
 CALCULATIONS FOR ALL ROOMS AND SPACES. PROVIDE A
 SCHEDULE THAT INCLUDES THE REQUIRED AND PROVIDED O/A
 AIR.
  
 2) CLARIFY HOW THE WAREHOUSE IS BEING VENTILATED. IS
 THERE AN EXISTING SYSTEM, OR WILLL A NEW SYSTEM BE
 PROVIDED- SECTION 401.2.
  