| Plan Review Notes For Permit 17040028 |
| Permit Number |
17040028 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-11 11:46:39 | PASS PROVISO | | | 1) PROVIDE A ENGINEER DETAIL ON CURB TO ROOF | | | AND RTU TO CURB TIE DOWN. AT FIRST INSPECTION. | | | PER SECTION 301.15 WIND RESISTANCE 2014 FBC (M) | | | 2) FAN SHUT DOWN REQUIRED FOR RTU 1 AND 2 | | | PER SECTION 606.2.1 RETURN AIR SYSTEM. 2014 FBC (M) | | | 3) REFER TO SECTION 606.4.1 SUPERVISION AND SECTION | | | 606.3 INSTALLATION 2014 FBC (M) | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|