| 2017-04-25 17:45:27 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. TUB DRAIN SHALL CONNECT TO WET VENT SEPARATELY FROM |
| | WATER CLOSE BRANCH DRAIN. PER FBC RES P3108.1 |
| | HORIZONTAL WET VENT PERMITTED. |
| | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS |
| | LOCATED ON THE SAME FLOOR LEVEL SHALL BE PERMITTED TO |
| | BE VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL |
| | BE CONSIDERED THE VENT FOR THE FIXTURES AND SHALL |
| | EXTEND FROM THE CONNECTION OF THE DRY VENT ALONG THE |
| | DIRECTION OF THE FLOW IN THE DRAIN PIPE TO THE MOST |
| | DOWNSTREAM FIXTURE DRAIN CONNECTION. EACH FIXTURE DRAIN |
| | SHALL CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH |
| | BEING WET VENTED OR SHALL HAVE A DRY VENT. EACH |
| | WET-VENTED FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO |
| | THE HORIZONTAL WET VENT. ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUPS SHALL CONNECT TO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE HORIZONTAL WET VENT. |
| | |
| | |
| | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT |
| | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL |
| | COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |