| Plan Review Notes For Permit 17040017 |
| Permit Number |
17040017 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2017-06-29 17:14:25 | APPROVED WITH EXCEPTIONS | | | "BUILDING PROVISO" | | | | | | 1) SUBMIT A SIGNED AND SEALED DETAIL FROM THE | | | ARCHITECT, STEVE SIEBERT, THAT SPECIFIES THE SIZE AND | | | SPECIES OF THE LEDGER SUPPORTING THE ROOF TRUSSES, AS | | | WELL AS, THE TYPE AND SPACING OF THE FASTENERS THAT | | | WILL BE USED TO ATTACH IT TO THE CONCRETE TIE BEAM. | | | FBC-R301.1 | | | | | | 2) GAF BUR SYSTEM, NOA NO.13-1022.15 PROVISO: SPECIFY | | | THE APPROVED ASSEMBLY, MAXIMUM DESIGN PRESSURE AND | | | PROVIDE TWO SETS OF SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR ENHANCED FASTENING AS REQUIRED BY | | | LIMITATION #7 OF THE NOA. NOTE: THE PLANS SPECIFY 1" | | | POLYISOCYANURATE INSULATION AS PART OF THE ROOFING | | | ASSEMBLY. FBC-R301.2.1 |
|