| 2017-05-04 11:51:51 | PLAN |
| | REVIEW COMMENTS |
| | |
| | 1ST REVIEW: FBC FIFTH EDITION (2014) |
| | ROBERT MCDOUGAL, CBO |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561) 805-6714 |
| | [email protected] |
| | |
| | DENIED BY BUILDING |
| | PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| | |
| | 1) SUBMIT TWO SETS OF A SURFACE WATER DRAINAGE PLAN |
| | THAT SHOWS COMPLIANCE WITH FBC-R 401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| | SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| | FIRST 10 FEET (3048 MM). |
| | |
| | 2) THIS PROJECT IS UNDER THE 2014 FBC. THERE ARE |
| | REFERENCES TO THE 2010 FBC UNDER THE STRUCTURAL NOTES |
| | ON SHEET S.1. PLEASE REVISE. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC-R318.1 FOR TERMITE |
| | PROTECTION. |
| | |
| | 4) SHOW COMPLIANCE WITH FBC-R318.5 CONDENSATE LINES, |
| | IRRIGATION/SPRINKLER SYSTEM RISERS FOR SPRAY HEADS, AND |
| | ROOF DOWNSPOUTS SHALL DISCHARGE AT LEAST 1 FOOT (305 |
| | MM) AWAY FROM THE STRUCTURE SIDEWALL, WHETHER BY |
| | UNDERGROUND PIPING, TAIL EXTENSIONS OR SPLASH BLOCKS. |
| | GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON ALL BUILDINGS |
| | WITH EAVES OF LESS THAN 6 INCHES (152 MM) HORIZONTAL |
| | PROJECTION EXCEPT FOR GABLE END RAKES OR ON A ROOF |
| | ABOVE ANOTHER ROOF. |
| | |
| | 5) THE PLANS DO NOT SPECIFY ANY REINFORCEMENT IN THE 4" |
| | CONCRETE FLOOR SLAB. DUE TO THE SOIL CONDITIONS, IT IS |
| | REQUIRED THAT THE SLAB IS LIGHTLY REINFORCED USING 6 X |
| | 6 WELDED WIRE FABRIC. FBC-R506.1 & ACI 332 |
| | |
| | 6) SPECIFY THE SLOPE OF THE HIP ROOF ON THE PLANS. |
| | FBC107.2.1 |
| | |
| | 7) PROVIDE WINDOW AND DOOR BUCK DETAILS ON THE PLANS. |
| | |
| | 8) PROVIDE STRUCTURAL DETAILS FOR THE LEDGERS THAT ARE |
| | SUPPORTING THE ROOF TRUSSES. |
| | |
| | 9) PROVIDE THE ROOF UPLIFT VALUES FOR A 10 SQFT |
| | EFFECTIVE WIND AREA. |
| | |
| | 10) IN THE TABLE ON SHEET S.3 THE ROOF UPLIFT VALUES |
| | FOR ZONES 2 AND 3 ARE IDENTICAL. THE PARAPET IS |
| | REQUIRED TO BE 3 FEET HIGH AROUND THE ENTIRE PERIMETER |
| | OF THE ROOF IN ORDER FOR THE ZONE 2 (PERIMETER) |
| | PRESSURES TO BE THE SAME AS THE ZONE 3 (CORNER) |
| | PRESSURES. ACSE 7 - 10. |
| | |
| | 11) PROVIDE SCUPPER SIZING CALCULATIONS. FBC 107.2.1 & |
| | FBC- PLUMBING 1106.7 |
| | |
| | 12) R903.4.1 OVERFLOW DRAINS AND SCUPPERS. WHEN OTHER |
| | MEANS OF DRAINAGE OF OVERFLOW WATER IS NOT PROVIDED, |
| | OVERFLOW SCUPPERS SHALL BE PLACED IN WALLS OR PARAPETS |
| | NOT LESS THAN 2 INCHES (51 MM) NOR MORE THAN 4 INCHES |
| | (102 MM) ABOVE THE FINISHED ROOF COVERING AND SHALL BE |
| | LOCATED AS CLOSE AS PRACTICAL TO REQUIRED VERTICAL |
| | LEADERS OR DOWNSPOUTS OR WALL AND PARAPET SCUPPERS. AN |
| | OVERFLOW SCUPPER SHALL BE SIZED IN ACCORDANCE WITH THE |
| | FLORIDA BUILDING CODE, PLUMBING. |
| | |
| | 13) THE PLANS SHOW LOUVERED WALL ATTIC VENTS ON SHEET |
| | A.2 AND THE ENERGY FORM SPECIFIES AN UNVENTED ATTIC. |
| | PLEASE CLARIFY FBC 107.2.1 |
| | |
| | 14) IF THE ATTIC IS VENTED PROVIDE THE NET FREE AREA OF |
| | THE VENTS AND THE CALCULATIONS FOR MINIMUM VENT AREA |
| | PER FBC - R806.2 |
| | |
| | 15) IF THIS IS AN UNVENTED ATTIC SHOW THAT IT COMPLIES |
| | WITH FBC-R806.5 UNVENTED ATTIC AND UNVENTED ENCLOSED |
| | RAFTER ASSEMBLIES. UNVENTED ATTIC ASSEMBLIES (SPACES |
| | BETWEEN THE CEILING JOISTS OF THE TOP STORY AND THE |
| | ROOF RAFTERS) AND UNVENTED ENCLOSED RAFTER ASSEMBLIES |
| | (SPACES BETWEEN CEILINGS THAT ARE APPLIED DIRECTLY TO |
| | THE UNDERSIDE OF ROOF FRAMING MEMBERS/RAFTERS AND THE |
| | STRUCTURAL ROOF SHEATHING AT THE TOP OF THE ROOF |
| | FRAMING MEMBERS/RAFTERS) SHALL BE PERMITTED IF ALL THE |
| | FOLLOWING CONDITIONS ARE MET: |
| | |
| | 1. THE UNVENTED ATTIC SPACE IS COMPLETELY CONTAINED |
| | WITHIN THE BUILDING THERMAL ENVELOPE. |
| | |
| | 2. NO INTERIOR CLASS I VAPOR RETARDERS ARE INSTALLED ON |
| | THE CEILING SIDE (ATTIC FLOOR) OF THE UNVENTED ATTIC |
| | ASSEMBLY OR ON THE CEILING SIDE OF THE UNVENTED |
| | ENCLOSED RAFTER ASSEMBLY. |
| | |
| | 3. WHERE WOOD SHINGLES OR SHAKES ARE USED, A MINIMUM |
| | 1/4- INCH (6 MM) VENTED AIR SPACE SEPARATES THE |
| | SHINGLES OR SHAKES AND THE ROOFING UNDERLAYMENT ABOVE |
| | THE STRUCTURAL SHEATHING. |
| | |
| | 4. IN CLIMATE ZONES 5, 6, 7 AND 8 OF TABLE R301.1 OF |
| | THE FLORIDA BUILDING CODE, ENERGY CONSERVATION, ANY |
| | AIRIMPERMEABLE INSULATION SHALL BE A CLASS II VAPOR |
| | RETARDER, OR SHALL HAVE A CLASS III VAPOR RETARDER |
| | COATING OR COVERING IN DIRECT CONTACT WITH THE |
| | UNDERSIDE OF THE INSULATION. |
| | |
| | 5. EITHER ITEMS 5.1, 5.2 OR 5.3 SHALL BE MET, DEPENDING |
| | ON THE AIR PERMEABILITY OF THE INSULATION DIRECTLY |
| | UNDER THE STRUCTURAL ROOF SHEATHING. |
| | |
| | 5.1. AIR-IMPERMEABLE INSULATION ONLY. INSULATION SHALL |
| | BE APPLIED IN DIRECT CONTACT WITH THE UNDERSIDE OF THE |
| | STRUCTURAL ROOF SHEATHING. |
| | |
| | 5.2. AIR-PERMEABLE INSULATION ONLY. IN ADDITION TO THE |
| | AIR-PERMEABLE INSULATION INSTALLED DIRECTLY BELOW THE |
| | STRUCTURAL SHEATHING, RIGID BOARD OR SHEET INSULATION |
| | SHALL BE INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF |
| | SHEATHING AS SPECIFIED IN TABLE R806.5 FOR CONDENSATION |
| | CONTROL. |
| | |
| | 5.3. AIR-IMPERMEABLE AND AIR-PERMEABLE INSULATION. THE |
| | AIR-IMPERMEABLE INSULATION SHALL BE APPLIED IN DIRECT |
| | CONTACT WITH THE UNDERSIDE OF THE STRUCTURAL ROOF |
| | SHEATHING AS SPECIFIED IN TABLE R806.5 FOR CONDENSATION |
| | CONTROL. THE AIR-PERMEABLE INSULATION SHALL BE |
| | INSTALLED DIRECTLY UNDER THE AIR-IMPERMEABLE |
| | INSULATION. |
| | |
| | 5.4. WHERE PREFORMED INSULATION BOARD IS USED AS THE |
| | AIR-IMPERMEABLE INSULATION LAYER, IT SHALL BE SEALED AT |
| | THE PERIMETER OF EACH INDIVIDUAL SHEET INTERIOR SURFACE |
| | TO FORM A CONTINUOUS LAYER. |
| | |
| | 16) SUBMIT THE PRODUCT EVALUATION REPORT OF THE SPRAY |
| | FOAM INSULATION (IF APPLICABLE). FBC-R316 |
| | |
| | 17) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS |
| | FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC |
| | 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE |
| | BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER |
| | OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH |
| | FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS |
| | AND MAXIMUM DESIGN PRESSURES FOR EACH OF THE DIFFERENT |
| | ROOFING MATERIALS, AND THE CASEMENT WINDOWS. |
| | |
| | 18) SUBMIT AN ADDITIONAL SET OF PRODUCT APPROVALS FOR |
| | THE ONES THAT WERE SUBMITTED. TWO SETS ARE REQUIRED. |
| | FBC 107.3.4 |
| | |
| | 19) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT |
| | A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW |
| | COMMENTS HAS BEEN ADDRESSED. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |