| Plan Review Notes For Permit 17040007 |
| Permit Number |
17040007 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-02 06:11:17 | 1) A SERVICE SINK IS REQUIRED IN THIS SPACE PER 2014 | | | FBC-PLUMBING TABLE 403.1. | | | 2) SHT. A-4 - DEATAIL #2 - TRANSFER SHOWER DIMENSIONS | | | SHALL BE 36 INCHES BY 36 INCHES CLEAR INSIDE | | | DIMENSIONS. SHOW THIS ON THE DETAIL. FBC-ACCESS. | | | SEC.608.2.1. | | | 3) L-SHAPED SHOWER SEATS SHALL BE LOCATED PER 2014 | | | FBC-ACCESS SEC.610.3.2. | | | 4) THE SHOWER CONTROLS IN THE ACCESSIBLE SHOWERS SHALL | | | BE LOCATED PER 2014 FBC-ACCESS. SEC.608..5.1. SHOW THE | | | DIMENSIONS ON THE PLANS. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|