2017-04-07 15:31:481ST REVIEW FBC-2014 MECHANICAL
 PERMIT #1704007
 4/7/17
  
 1) M0.1 & M1.1: SCOPE OF WORK NOTE #1 INDICATES ONE NEW
 VAV BOX, THE PLANS AND O/A CALCULATIONS INDICATE ALL
 EXISTING.
  
 2) PROVIDE EQUIPMENT SCHEDULES FOR THE VAV BOXES-
 MAKES, MODEL NUMBERS AND CAPACITIES.
  
 3) PLEASE PROVIDE A VAV BOX SUPPORT AND DUCT CONNECTION
 DETAIL.
  
 4) PLACE A NOTE ON THE PLAN INDICATING ABOVE CEILING
 PLENUM SPACE.
  
 5) M1.1: SHOW THE POINT OF CONNECTION OF THE NEW TOILET
 EXHAUST DUCT TO THE EXISTING.
  