| 2017-08-15 08:14:01 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PREVIOUS COMMENT #1 NOT ADDRESSED SATISFACTORILY. |
| | ONE PLAN WAS NOT SIGNED, 1 PLAN WAS SIGNED BY "CHARLES |
| | JACKSON", WHO IS NOT A LICENSED DESIGN PROFESSIONAL PER |
| | FDBPR WEBSITE. PLAN IS REQUIRED TO BE SIGNED AND SEALED |
| | BY A LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL |
| | CONTRACTOR QUALIFIER. FS 471, 481; FBC 107.2.1 |
| | 2. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY. |
| | PROVIDE SWITCHED LIGHT AT EXTERIOR DOOR OF BATHROOM PER |
| | PREVIOUS COMMENT. NEC 210.70(A)(2)(B), FBC RE3903.3 |
| | 3. PREVIOUS COMMENT #5 NOT ADDRESSED SATISFACTORILY. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET. |
| | OUTLETS ARE NOT SHOWN IN AREA ADJACENT TO THE PROPESED |
| | WORK AREA. SHOW AS EITHER EXISTIG OF NEW. PROVIDE |
| | CORRECTION. NEC 210.52; FBC RE3901.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |