2017-08-15 08:14:01CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PREVIOUS COMMENT #1 NOT ADDRESSED SATISFACTORILY.
 ONE PLAN WAS NOT SIGNED, 1 PLAN WAS SIGNED BY "CHARLES
 JACKSON", WHO IS NOT A LICENSED DESIGN PROFESSIONAL PER
 FDBPR WEBSITE. PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY A LICENSED DESIGN PROFESSIONAL OR THE ELECTRICAL
 CONTRACTOR QUALIFIER. FS 471, 481; FBC 107.2.1
 2. PREVIOUS COMMENT #2 NOT ADDRESSED SATISFACTORILY.
 PROVIDE SWITCHED LIGHT AT EXTERIOR DOOR OF BATHROOM PER
 PREVIOUS COMMENT. NEC 210.70(A)(2)(B), FBC RE3903.3
 3. PREVIOUS COMMENT #5 NOT ADDRESSED SATISFACTORILY.
 RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL
 SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE OUTLET.
 OUTLETS ARE NOT SHOWN IN AREA ADJACENT TO THE PROPESED
 WORK AREA. SHOW AS EITHER EXISTIG OF NEW. PROVIDE
 CORRECTION. NEC 210.52; FBC RE3901.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  