Plan Review Notes
Plan Review Notes For Permit 17040006
Permit Number 17040006
Review Stop E
Sequence Number 3
Notes
Date Text
2017-06-26 07:57:42CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE
  
 ELECTRICAL REVIEW COMMENTS:
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED
 BY A DESIGN PROFESSIONAL OR ELECTRICAL CONTRACTOR
 QUALIFIER. FS 471.025; 471.003(2)(H)
 2. PROVIDE LIGHT AT EXTERIOR DOOR. "FOR DWELLING UNITS,
 ATTACHED GARAGES, AND DETACHED GARAGES WITH ELECTRIC
 POWER, AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING
 OUTLET SHALL BE INSTALLED ON THE EXTERIOR SIDE OF
 OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS".
 NEC 210.70(A)(2)(B), FBC RE3903.3
 3. PROVIDE FLOOR PLAN OF HOUSE SHOWING LOCATIONS OF
 EXISTING SMOKE ALARMS. IF NONE ARE EXISTING, OR NOT TO
 CODE, SHOW AS NEW INSTALLATIONS. FBC R314, R315; FBC
 107.2.1
 4. PROVIDE PANEL SCHEDULE SHOWING ANY NEW OR ALTERED
 CIRCUITS, INCLUDE WIRE AND BREAKER SIZE AND TYPE. NEC
 408.4; FBC RE3706.2; FBC 107.2.1
 5. PROVIDE FLOOR PLAN OF AREA WHERE WORK IS PROPOSED
 INDICATING ANY EXISTING, RELOCATED, OR NEW POWER AND
 LIGHTING OUTLETS. FBC 107.2.1
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
  