| Date |
Text |
| 2017-06-26 07:57:42 | CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | |
| | ELECTRICAL REVIEW COMMENTS: |
| | |
| | 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED AND SEALED |
| | BY A DESIGN PROFESSIONAL OR ELECTRICAL CONTRACTOR |
| | QUALIFIER. FS 471.025; 471.003(2)(H) |
| | 2. PROVIDE LIGHT AT EXTERIOR DOOR. "FOR DWELLING UNITS, |
| | ATTACHED GARAGES, AND DETACHED GARAGES WITH ELECTRIC |
| | POWER, AT LEAST ONE WALL SWITCH-CONTROLLED LIGHTING |
| | OUTLET SHALL BE INSTALLED ON THE EXTERIOR SIDE OF |
| | OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL ACCESS". |
| | NEC 210.70(A)(2)(B), FBC RE3903.3 |
| | 3. PROVIDE FLOOR PLAN OF HOUSE SHOWING LOCATIONS OF |
| | EXISTING SMOKE ALARMS. IF NONE ARE EXISTING, OR NOT TO |
| | CODE, SHOW AS NEW INSTALLATIONS. FBC R314, R315; FBC |
| | 107.2.1 |
| | 4. PROVIDE PANEL SCHEDULE SHOWING ANY NEW OR ALTERED |
| | CIRCUITS, INCLUDE WIRE AND BREAKER SIZE AND TYPE. NEC |
| | 408.4; FBC RE3706.2; FBC 107.2.1 |
| | 5. PROVIDE FLOOR PLAN OF AREA WHERE WORK IS PROPOSED |
| | INDICATING ANY EXISTING, RELOCATED, OR NEW POWER AND |
| | LIGHTING OUTLETS. FBC 107.2.1 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |