| Plan Review Notes For Permit 17031290 |
| Permit Number |
17031290 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-13 15:53:10 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17031290 | | | 4/13/17 | | | | | | 1) THE WORK DESCRIPTION ON THE APPLICATION READS | | | "INSTALL 4 FANS & DUCTWORK". THE SUBMITTED PLANS AND | | | FAN SCHEDULE SHOW 20 FANS. I AM ASSUMING THE FANS TO BE | | | INSTALLED ARE FOR THE KITCHEN HOODS, HOWEVER THERE ARE | | | ONLY TWO GREASE EXHAUST FANS- ( EF-16 & 18) AND ONE | | | DISHWASHER EXHAUST FAN- (EF-15) SHOWN ON THE PLANS AND | | | THE SCHEDULE. PLEASE PROVIDE MORE SPECIFIC | | | | | | INFORMATION ON THE APPLICATION AND ON THE PLANS. | | | | | | 2) CLARIFY IF THE GREASE EXHAUST DUCTS WILL BE | | | INSTALLED 18" CLEAR OF COMBUSTIBLES OR IF DUCTWRAPPING | | | WILL BE INSTALLED. PROVIDE NOTES ON THE PLAN AND SUBMIT | | | A PRODUCT DATA SHEET FOR THE WRAP IF APPLICABLE TO THE | | | PROJECT. | | | | | | 3) PROVIDE A ROOF PLAN THAT SHOWS CLEARANCE DISTANCE | | | MEASUREMENTS FROM THE GREASE EXHAUST TERMINATIONS TO | | | MECHANICAL OR GRAVITY AIR INTAKES- SEE SECTION | | | 506.3.13.3. | | | | | | 4) PROVIDE A DETAIL THAT SHOWS THE CLEARANCE DISTANCE | | | HEIGHT FROM THE THE ROOF SURFACE TO THE EXHAUST OUTLET- | | | SECTION 506.3.13.1. | | | | | | 5) PROVIDE WIND LOAD ENGINEERING FOR ANCHORING THE FANS | | | AND FAN CURBS TO THE ROOF STRUCTURE- SECTION 301.15. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|