2017-07-07 17:28:20BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17031283
 ADD: 8225 IBIS BLVD.
 CONT:DENNIE H NEW CONSTRUCTION CO.
 TEL: 772-201-8444
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
 2ND REVIEW
 DATE: FRI. JULY 07/ 2017
 ACTION: DENIED
  
 1) COMPLIED. 2014 FBC-ENERGY. C101.4.5 CHANGE IN SPACE
 CONDITIONING.
  
 2) COMPLIED.
  
 3)2ND REQUEST. THE RESPONSE FROM THE DESIGNER OF RECORD
 INDICATES THE EXISTING FRONT DOOR, SIDELIGHTS,
 HORIZONTAL MULLION AND TRANSOM ARE TO BE RELOCATED. W.
 P. B. ADMINISTRATIVE CODE 104.9.1 USED MATERIALS AND
 EQUIPMENT. THE USE OF USED, RECYCLED, OR RECLAIMED
 MATERIALS WHICH MEET THE REQUIREMENTS OF THIS CODE FOR
 NEW MATERIALS IS PERMITTED. USED EQUIPMENT AND DEVICES
 SHALL NOT BE REUSED UNLESS APPROVED BY THE BUILDING
 OFFICIAL. THE BUILDING OFFICIAL HAS APPROVED THE REUSE
 OF THE EXISTING SYSTEM, BUT THE CONTRACTOR WILL NEED TO
 PRODUCE THE PRODUCT APPROVAL AND IDENTIFY ALL OF THE
 COMPONENTS ASKED IN COMMENT # 4 WITH THE INSTALLATION
 FOR THE CORRESPONDING PRESSURES.
 1ST REVIEW COMMENT. 2014 FBC-B 1609.1.2 PROTECTION OF
 OPENINGS, 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA
 DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE
 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY
 OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS ,SIDE LIGHTS, HORIZONTAL MULLION
 & TRANSOM
  
 4) 2ND REQUEST SEE COMMENT ABOVE. IDENTIFY GLAZING/
 MULLIONS. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION INFORMATION IF REQUIRED, ATTACHMENTS AND
 ASSOCIATE PRESSURES FOR EACH OPENING SIZE. 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURERS INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 5) 2ND REQUEST. SEE COMMENT # 3, REQUIRES THE DESIGNER
 OF RECORD REVIEW. FBC 107.3.4.1 PRODUCT APPROVALS.
 THOSE PRODUCTS WHICH ARE REGULATED BY THE DCA RULE
 9N-03 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6) 2ND REQUEST. IMPACT FEES. BEFORE A PERMIT TO
 CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF PLANS MUST
 BE STAMPED BY THAT OFFICE, AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved