Plan Review Notes
Plan Review Notes For Permit 17031283
Permit Number 17031283
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-19 11:15:521ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17031283
 4/19/17
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW MITSUBISHI SYSTEM IN COMPLIANCE WITH SECTION
 C403.2.1 FBC-14 ENERGY CONSERVATION.
  
 2) THE LOBBY IS DEFINED AS AN ADDITION IN ACCORDANCE
 WITH SECTION 202 FBC-14 ENERGY CONSERVATION. REFER TO
 SECTION C101.4.3 AND C401.2 AND SUBMIT COMPLIANCE
 DOCUMENTATION- SECTION C101.5.1.
  
 3) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE CONDENSER AND MOUNTING PAD- SECTION 301.15
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  