| 2017-04-21 16:58:51 | |
| | 04/21/17 |
| | PHONE CONVERSATION BETWEEN ROBERT BROWN AND LARRY |
| | GEORGE (ENGINEER) TO GO OVER BELOW COMMENTS. |
| | NOTE: ROBERT BROWN TOLD LARRY GEORGE THAT HE NEEDS TO |
| | DO THE DOOR INSTALLATION INSPECTION AND PROVIDE LETTER |
| | CERTIFYING THAT DOORS WERE BUILT AND INSTALLED PER HIS |
| | DESIGN. HE AGREED. |
| | |
| | |
| | |
| | RESIDENTIAL (R3) SUBMITTAL BUILDING REVIEW COMMENTS. |
| | CODE: FBC 5TH EDITION(2014). |
| | |
| | 1- CUSTOM DOORS: CUSTOM DOORS NEED TO BE TESTED BY AN |
| | APPROVED TESTING LABORATORY OR ENGINEERED AS REQUIRED |
| | BY SEC. R612.2.1 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| | ENGINEERED PACKAGE SUBMITTED NEEDS THE FOLLOWING FOR |
| | BUILDING OFFICIAL REVIEW AND APPROVAL: |
| | A) PROVIDE CURRENT APPROVED PRODUCT APPROVAL FOR |
| | SIMILAR DOORS THAT ARE LESS OR EQUIVALENT IN |
| | PERFORMANCE THAN THE PROPOSED DOORS FOR COMPARISON. |
| | ENGINEER TO PROVIDE COMPLETE COMPARATIVE ANALYSIS |
| | INFORMATION SHOWING THAT PROPOSED DOORS WILL MEET OR |
| | EXCEED THE PERFORMANCE OF THE APPROVED DOORS. NOTE: IN |
| | ORDER TO AVOID CONFLICTS OR DELAYS THE ENGINEER IS |
| | ADVISED TO SEE SEC. R612.3.1 FBC-RESIDENTIAL AND THE |
| | EXCEPTIONS TO USE AS A REFERENCE AS TO WHAT IS THE |
| | INFORMATION THAT NEEDS TO BE SUBMITTED FOR "COMPARATIVE |
| | ANALYSIS" FOR REVIEW. |
| | |
| | B) DRAWINGS SUBMITTED ARE INCOMPLETE AND INCORRECT. |
| | THERE ARE DRAWINGS SUBMITTED THAT DON'T APPLY TO THE |
| | PROPOSED CUSTOM DOORS. THERE IS NO GLAZING IN THE |
| | PROPOSED DOORS, THEREFORE THE ASTRO GUARD INFORMATION |
| | SUBMITTED IS NOT REQUIRED. ENGINEER TO PROVIDE ONLY THE |
| | DETAILS AND SPECIFICATIONS THAT MATCHES THE PROPOSED |
| | CUSTOM DOORS ASSEMBLY. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | C) ENGINEER TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE INSTALLATION OF THE DOORS FRAME |
| | TO THE OPENING ACTUAL CONDITIONS. THERE IS NOT WOODEN |
| | INFILL OPENING AS SPECIFIED ON THE SECOND PAGE OF THE |
| | LETTER SUBMITTED BY LAWRENCE L. GEORGE. SEE PLANS FOR |
| | CORRECT SUBSTRATE ON ALL SIDES AND PROVIDE COMPLETE |
| | DETAILS AND SPECIFICATIONS FOR ALL CONDITIONS. SEC. |
| | R301.1 FBC-RESIDENTIAL. |
| | |
| | D) ENGINEER TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE CONSTRUCTION OF THE DOORS. |
| | SPECIFY PANELS SIZES, THICKNESS, REINFORCEMENT, WELDING |
| | SPECIFICATIONS, ETC. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | E ) ENGINEER TO TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE CONSTRUCTION OF DOORS FRAME. |
| | SPECIFY THE DOOR FRAME THICKNESS AND WELDING |
| | SPECIFICATIONS OR CORNER ATTACHMENT SPECIFICATIONS. |
| | SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | F) ENGINEER TO TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE ATTACHMENT OF THE DOORS FRAME AT |
| | THE HEAD OF THE DOOR. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | G) ENGINEER TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE EXTERIOR TABS. SPECIFY THICKNESS |
| | AND WELDING SPECIFICATIONS TO THE DOOR FRAME. NOTE: |
| | ALSO, TAKE INTO CONSIDERATION ATTACHMENT TO THE |
| | STOREFRONT SYSTEM AS SHOWN ON PLANS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | H) ENGINEER TO TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE ATTACHMENT OF THE DOORS FRAME AT |
| | THE HEAD OF THE DOORS. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | I) ENGINEER TO TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE ATTACHMENT OF THE DOORS |
| | THRESHOLD. SEC. R301.1 FBC-RESIDENTIAL. |
| | |
| | J) ENGINEER TO TO PROVIDE COMPLETE DETAILS AND |
| | SPECIFICATIONS FOR THE DOORS HINGES. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | K) ENGINEER RESPONSIBLE FOR THE DESIGN NEEDS TO SIGN |
| | AND SEAL (ORIGINAL) EACH SHEET AS REQUIRED BY FAC |
| | 61G15-23.002 AND CHAPTER 471 FLORIDA STATUTE. |
| | |
| | L) ENGINEER RESPONSIBLE FOR THE DESIGN NEEDS TO PROVIDE |
| | HIS TILE BLOCK WITH ALL THE REQUIRED INFORMATION ON |
| | EACH SHEET AS REQUIRED BY FAC 61G15-23.002 AND CHAPTER |
| | 471 FLORIDA STATUTE. |
| | |
| | 2- ENGINEER OF RECORD ON THIS HOUSE NEEDS TO REVIEW AND |
| | APPROVE IN WRITING (NOT SIGNING AND SEALING) THIS |
| | PRODUCT APPROVAL PRIOR TO SUBMITTAL TO THIS OFFICE. |
| | SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |