| 2017-04-28 07:51:44 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17031256 |
| | 4/28/17 |
| | |
| | 1) THE PERMIT APPLICATION INDICATES INSTALLATION OF 3 |
| | WALK-IN COOLERS ON THE INTERIOR AND 1 EXTERIOR WALK-IN |
| | COOLER/FREEZER COMBO UNIT, HOWEVER THERE ARE ONLY SPECS |
| | SUBMITTED FOR 1 INTERIOR AND 1 EXTERIOR UNIT- PLEASE |
| | PROVIDE A COMPLETE SUBMITTAL PACKAGE THAT INCLUDES |
| | SPECS FOR ALL THE WALK-IN BOXES. |
| | |
| | 2) SUBMIT A FLORIDA PRODUCT APPROVAL FOR THE |
| | AMERIKOOLER EXTERIOR WALK-IN BOX, OR PROVIDE |
| | DOCUMENTATION INDICATING THAT THE UNIT HAS FLORIDA |
| | APPROVAL AS A MANUFACTURED BUILDING- SEE FAC RULE 9N-B. |
| | IN LIEU OF ANY DOCUMENTATION OF APPROVAL BY EITHER |
| | FLORIDA AGENCY, COMPLETE ENGINEERING CERIFICATION BY A |
| | THIRD-PARTY AGENCY WILL HAVE TO PROVIDED. |
| | |
| | 3) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | THE EXTERIOR WALK-IN BOX- SECTION 301.15. |
| | |
| | 4) PROVIDE REFRIGERATION PLANS FOR THE WALK-IN BOXES |
| | INCLUDING EQUIPMENT SCHEDULES THAT INDICATE MAKES AND |
| | MODELS OF CONDENSERS AND EVAPORATORS, PIPING DETAILS |
| | AND PIPING RUNS, AND LOCATIONS OF EQUIPMENT. PLEASE |
| | NOTE THAT WIND LOAD ENGINEERING IS REQUIRED FOR |
| | INSTALLATION OF EXTERIOR CONDENSERS- SECTION 301.15. |
| | |
| | 5) PROVIDE CONDENSATE DISPOSAL PLANS FOR THE |
| | EVAPORATORS THAT INCLUDES THE TRYPES AND SIZES OF |
| | CONDENSATE PIPING, PIPING RUNS AND DISCHARGE LOCATIONS- |
| | SECTION 307. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |