| 2017-06-22 13:18:42 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 17031256 |
| | W. P. B. PERMIT: 16050258 |
| | ADD: 209 6TH ST. |
| | CONT: OWNER BUILDER ALLIANCES |
| | TEL: 561-254-6779 |
| | E-MAIL: [email protected], |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | DATE: FRI. JULY 22/2016 |
| | ACTION: DENIED |
| | |
| | 1) THE SUBMITTED COOLER/ FREEZER PLANS DO NOT HAVE |
| | APPROVAL FOR THE EXTERIOR OF THE BUILDING. IF SO PLEASE |
| | SUBMIT STATE APPROVAL. THIS HAS BEEN VERIFIED BY THE |
| | MECHANICAL PLAN REVIEWER THIS MANUFACTURER HAS NO STATE |
| | APPROVAL FOR THE COOLER/ FREEZER UNITS FOR EXTERNAL |
| | USE. PLEASE NOTE THE S2 & S3 SHEETS DO NOT PROVIDE |
| | ENOUGH DETAILS. SHEET S2 HAS A CUT SECTION 9/S3 SHOWN |
| | FOR BOTH THE EAST AND WEST ELEVATIONS SHOWING THE WALLS |
| | ENCLOSED AND BENEATH THE ROOF STRUCTURE, AND 2 LAYERS |
| | OF BOARD ON BOARD SCREEN WALL. |
| | IT WOULD APPEAR THERE ARE NO OPENINGS TO ENTER THIS |
| | MECHANICAL ROOM. I?VE GONE TO THE APPROVE PLANS FOR |
| | VERIFICATION OF WHAT WAS APPROVED. SHEET A001.1 SHOWS |
| | THE WEST FACE OF THE STRUCTURE IS TO BE 5 FT. -1 IN. |
| | FROM THE PROPERTY LINE. SHEET A008 SHOWS THE EAST, |
| | NORTH AND WEST ELEVATIONS OF THIS AREA. THE EAST WALL |
| | DOES SHOW AN OPENING AS LARGE AS A GARAGE DOOR. THE |
| | NORTH WALL NO OPENINGS, AND THE WEST WALL AS OPEN. THIS |
| | IS A CODE VIOLATION; THE PLANS SHOULD NOT HAVE BEEN |
| | ISSUED WITH THE WEST FACE OPEN. SINCE THE STRUCTURE IS |
| | 5 FT. 1 INCH FROM THE PROPERTY LINE THIS WALL SHOULD BE |
| | 1 HOUR RATED. THIS IS PROTECT THIS PROPERTY AS WELL AS |
| | THE NEIGHBORING PROPERTY FROM FIRE, SEE 2014 FBC-B |
| | TABLE 602 FOR ALL BUILDING TYPES AND OCCUPANCIES. |
| | |
| | THE OTHER ISSUE THAT WOULD NEED TO BE ADDRESSED SINCE |
| | THE PLANS DO NOT STATE IF THIS STRUCTURE IS DESIGNED AS |
| | AN ENCLOSED OR PARTIALLY ENCLOSED STRUCTURE. SHEET S1 |
| | INDICATES THE MAIN BUILDING TO BE DESIGNED AS AN |
| | ENCLOSED STRUCTURE. 2014 FBC-B 1603.1.4 WIND DESIGN |
| | DATA. (4). APPLICABLE PRESSURE COEFFICIENT. PLEASE NOTE |
| | IF THE ENCLOSURE IS OPEN OR PARTIALLY OPEN THEN THE |
| | COOLER/ FREEZERS WILL HAVE TO HAVE BEEN TESTED FOR |
| | THESE CONDITIONS!!!!! |
| | |
| | IF THE DESIGNER ELECTS TO ENCLOSE THE STRUCTURE WITH A |
| | DOOR SYSTEM THEN AS STATED BY THE MECHANICAL REVIEWER |
| | AIR CIRCULATION AND VENTING MAYBE A CONCERN IF THE |
| | CONDENSERS ARE LOCATED WITHIN THIS ENCLOSED SPACE, |
| | LOUVERS AND NEED TO BE CONSIDERED AND PRODUCT APPROVALS |
| | . 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA |
| | DEPARTMENT OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE |
| | 61G20-3.005, RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY |
| | OF PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE |
| | PRODUCT APPROVALS: ( C ) WALL LOVERS. |
| | |
| | 2) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |