| 2017-04-25 12:46:11 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | 1ST REVIEW FBC 2014 EXISTING BUILDING |
| | |
| | MECHANICAL FAILED |
| | |
| | 1) SHEET M1 IS NOT SIGNED BY THE IDENTIFIED DESIGNER OF |
| | RECORD. M GONZALEZ IS LISTED. PLEASE SIGN PER THE |
| | FOLLOWING SECTION: |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | PLEASE NOTE TOU HAVE PROVIDED A NOTE ON THE EQUIPMENT |
| | SCHEDULE AS FOLLOWS: "OR EQUIVALENT." IT IS A BEST |
| | PRACTICE TO REMOVE SUCH NOTES AS THE INSTALLED |
| | EQUIPMENT MUST BE THE SPECIFIED EQUIPMENT UNLESS |
| | REVISED. NOTE THE SEER LISTED IS DIFFERENT THAN THE |
| | SEER LISTED ON THE ENERGY FORM. |
| | |
| | 2) FORM R405 PROVIDED IS NOT ACCURATELY COMPLETED. |
| | |
| | THE SEER LISTED OF 16.00 IS NOT CONSISTENT WITH THE |
| | SEER LISTED IN THE MECHANICAL EQUIPMENT SCHEDULE OF |
| | 14.00. THE FRONT SHEET OF THE FORM IS MISSING |
| | INFORMATION AT THE TOP AND IS MISSING THE OWNER'S |
| | REPERSENTATIVE OR OWNER'S SIGNATURE. |
| | |
| | FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| | AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| | (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| | SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| | COMPLIANCE BY SECTION 405. |
| | |