Plan Review Notes
Plan Review Notes For Permit 17031248
Permit Number 17031248
Review Stop M
Sequence Number 1
Notes
Date Text
2017-04-25 12:46:111ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL
 1ST REVIEW FBC 2014 EXISTING BUILDING
  
 MECHANICAL FAILED
  
 1) SHEET M1 IS NOT SIGNED BY THE IDENTIFIED DESIGNER OF
 RECORD. M GONZALEZ IS LISTED. PLEASE SIGN PER THE
 FOLLOWING SECTION:
 FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING
 DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN.
 PLEASE NOTE TOU HAVE PROVIDED A NOTE ON THE EQUIPMENT
 SCHEDULE AS FOLLOWS: "OR EQUIVALENT." IT IS A BEST
 PRACTICE TO REMOVE SUCH NOTES AS THE INSTALLED
 EQUIPMENT MUST BE THE SPECIFIED EQUIPMENT UNLESS
 REVISED. NOTE THE SEER LISTED IS DIFFERENT THAN THE
 SEER LISTED ON THE ENERGY FORM.
  
 2) FORM R405 PROVIDED IS NOT ACCURATELY COMPLETED.
  
 THE SEER LISTED OF 16.00 IS NOT CONSISTENT WITH THE
 SEER LISTED IN THE MECHANICAL EQUIPMENT SCHEDULE OF
 14.00. THE FRONT SHEET OF THE FORM IS MISSING
 INFORMATION AT THE TOP AND IS MISSING THE OWNER'S
 REPERSENTATIVE OR OWNER'S SIGNATURE.
  
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  