| Date |
Text |
| 2017-04-13 07:41:22 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PROVIDE SITE PLAN. |
| | FBC 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING |
| | OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| | AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION |
| | PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; ALL |
| | FENESTRATION PENETRATIONS; FLASHING; AND ROUGH OPENING |
| | DIMENSIONS; AND ALL EXTERIOR ELEVATIONS: |
| | |
| | 2. PROVIDE PRODUCT APPROVALS FOR EXT. DOOR AND OHD. |
| | FBC 107.3.4 - PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | SPECIFICALLY, PROVIDE AND DOOR SUBMITTALS. |
| | |
| | 3. PROVIDE ELECTRICAL PLAN. |
| | |
| | 4. PROVIDE A LANDING AT EXT. DOOR. |
| | R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| | EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE |
| | LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| | MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE |
| | DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE |
| | PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT |
| | VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT). |
| | |
| | 5. TRUSS ENGINEERING TO BE DEFERRED SUBMITTAL. |