| Plan Review Notes For Permit 17031171 |
| Permit Number |
17031171 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-31 12:38:15 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. IT IS NOT CLEAR WHERE THE PRODUCTS ARE PROPOSED. THE | | | PRODUCT APPROVALS INCLUDE MORE THAN ONE INSTALLATION | | | OPTION OR PRODUCT. | | | | | | PROVIDE A SCHEDULE, OR MARK UP THE ELEVATIONS, TO SHOW | | | LOCATIONS OF PRODUCTS PROPOSED. UNLESS A SHEDULE IS | | | PROVIDED BY SEOR, WORST CASE WILL BE USED FOR ALL | | | PRODUCTS (APPEARS TO BE +81/-117 ASD, +135/-195 LFRD) | | | SEE SHEETS S002, S003). | | | | | | FOR INSTANCE, SEE NOA 15-0430.04 PAGES 3-6, FOUR | | | DIFFERENT WIND DESIGN LOAD CHARTS, WHICH OPTION(S) DO | | | YOU PROPOSE? THE DPS RANGE FROM +67.9 TO 85, -67.9 TO | | | -145 (BASED ON GLASS TYPE, ANCHORING METHOD, SIZE). | | | | | | ON THE PRODUCT APPROVALS, INDICATE WHICH OPTION IS | | | PROPOSED. | | | | | | 2. SHOP DRAWING REVIEW STAMP DOES NOT INDICATE WHICH | | | PRODUCTS WERE REVIEWED, FBC 107, CLARIFY. | | | | | | | | | | | | | | | | | | | | | | | | |
|