| 2017-04-03 16:03:29 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) |
| | SHEET AC 1.00 - THERE IS A NOTE INDICATING EGRESS |
| | WINDOW INFORMATION. THERE IS ALSO A NOTE INDICATING A |
| | 2' 2" X 50" WINDOW DIMENSION. THERE IS INSUFFICIENT |
| | INFOMATION DEMONSTRATING COMPLIANCE FOR EGRESS WINDOWS. |
| | |
| | PER NFPA 101, CHAPTER 16, NEW DAYCARE OCCUPANCIES |
| | |
| | 16.2.11 SPECIAL MEANS OF EGRESS FEATURES. |
| | 16.2.11.1 WINDOWS FOR RESCUE. |
| | 16.2.11.1.1 EVERY ROOM OR SPACE NORMALLY SUBJECT TO |
| | CLIENT OCCUPANCY, OTHER THAN BATHROOMS, SHALL HAVE NOT |
| | LESS THAN ONE OUTSIDE WINDOW FOR EMERGENCY RESCUE THAT |
| | COMPLIES WITH ALL OF THE FOLLOWING, UNLESS OTHERWISE |
| | PERMITTED BY 16.2.11.1.2: |
| | (1) SUCH WINDOWS SHALL BE OPENABLE FROM THE INSIDE |
| | WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR |
| | OPENING OF NOT LESS THAN 20 IN. (510 MM) IN WIDTH, 24 |
| | IN. (610 MM) IN HEIGHT, AND 5.7 FT2 (0.5 M2) IN AREA. |
| | (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN 44 |
| | IN. (1120 MM) ABOVE THE FLOOR. |
| | (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID, |
| | WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE |
| | REQUIRED 5.7 FT2 (0.5 M2) OPENING AND A DEPTH OF NOT |
| | LESS THAN 20 IN. (510 MM), TO PASS FULLY THROUGH THE |
| | OPENING. |
| | |
| | PLEASE PROVIDE SPECIFIC WINDOW DETAIL |
| | SHOWING/INDICATING COMPLIANCE WITH ALL 3 REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 2) |
| | SHEET AC 1.00 - THERE IS NO DOOR SCHEDULE TO |
| | INDICATE/CONFIRM DOOR AND OPENING SIZE,INCLUDING |
| | BATHROOM DOORS, EXIT HARDWARE, LOCKS AND LATCHING, ETC. |
| | |
| | 16.2.2.2 DOORS. |
| | 16.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 16.2.2.2.2 PANIC HARDWARE OR FIRE EXIT HARDWARE. ANY |
| | DOOR IN A REQUIRED MEANS OF EGRESS FROM AN AREA HAVING |
| | AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| | PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF |
| | THE LATCH OR LOCK IS PANIC HARDWARE OR FIRE EXIT |
| | HARDWARE COMPLYING WITH 7.2.1.7. |
| | 16.2.2.2.3 SPECIAL LOCKING ARRANGEMENTS. |
| | 16.2.2.2.3.1 DELAYED-EGRESS LOCKING SYSTEMS COMPLYING |
| | WITH 7.2.1.6.1 SHALL BE PERMITTED. |
| | 16.2.2.2.3.2 ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES |
| | COMPLYING WITH 7.2.1.6.2 SHALL BE PERMITTED. |
| | 16.2.2.2.3.3 ELEVATOR LOBBY EXIT ACCESS DOOR ASSEMBLIES |
| | LOCKING IN ACCORDANCE WITH 7.2.1.6.3 SHALL BE |
| | PERMITTED. |
| | 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS, |
| | STORAGE AREAS, KITCHENS, AND OTHER SIMILAR SPACES OR |
| | AREAS SHALL BE SUCH THAT CLIENTS CAN OPEN THE DOOR FROM |
| | INSIDE THE SPACE OR AREA. |
| | 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| | SHALL BE DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR |
| | FROM THE OUTSIDE BY AN OPENING DEVICE THAT SHALL BE |
| | READILY ACCESSIBLE TO THE STAFF. |
| | |
| | PLEASE PROVIDE SPECIFIC DETAILS MEETING THE |
| | REQUIREMENTS. |
| | |
| | |
| | |
| | |
| | 3) |
| | SHEET AC 1.00 - THERE APPEARS TO BE A KITCHEN ROOM. ANY |
| | COOKING EQUIPMENT SHALL MEET THE REQUIRMETS OF NFPA 96 |
| | |
| | 16.3.2.3 COOKING FACILITIES SHALL BE PROTECTED IN |
| | ACCORDANCE WITH 9.2.3, UNLESS OTHERWISE PERMITTED BY |
| | 16.3.2.4 OR 16.3.2.5. |
| | 16.3.2.4 OPENINGS SHALL NOT BE REQUIRED TO BE PROTECTED |
| | BETWEEN FOOD PREPARATION AREAS AND DINING AREAS. |
| | 16.3.2.5 APPROVED DOMESTIC COOKING EQUIPMENT USED FOR |
| | FOOD WARMING OR LIMITED COOKING SHALL NOT BE REQUIRED |
| | TO BE PROTECTED. |
| | |
| | PLEASE PROVIDE A NOTE WITH INTENTIONS OR COMPLIANCE. |
| | |
| | |
| | |
| | 4) |
| | SHEET AC 1.00 - THERE IS AN INCORRECT"2015" REFERENCE |
| | TO THE CURRENT FFPC. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE, EFFECTIVE |
| | DECEMBER 31, 2014, INCLUDING THE 2012 EDITION OF NFPA 1 |
| | AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR |
| | STANDARDS. |
| | |
| | |
| | |
| | 5) |
| | SHEET AC 1.00 - THERE IS NO SITE PLAN SUBMITTED. A SITE |
| | PLAN IS REQUIRED SHOWING THE ENTIRE PROPERTY CONFIRMING |
| | ALL EXTS LEAD TO A PUBLIC WAY. |
| | |
| | 16.2.7 DISCHARGE FROM EXITS. DISCHARGE FROM EXITS SHALL |
| | BE ARRANGED IN ACCORDANCE WITH SECTION 7.7. |
| | |
| | 7.7 DISCHARGE FROM EXITS. |
| | 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| | DIRECTLY, AT A PUBLIC WAY OR AT AN EXTERIOR EXIT |
| | DISCHARGE, UNLESS OTHERWISE PROVIDED IN 7.7.1.2 THROUGH |
| | 7.7.1.4. |
| | 7.7.1.1 YARDS, COURTS, OPEN SPACES, OR OTHER PORTIONS |
| | OF THE EXIT DISCHARGE SHALL BE OF THE REQUIRED WIDTH |
| | AND SIZE TO PROVIDE ALL OCCUPANTS WITH A SAFE ACCESS TO |
| | A PUBLIC WAY. |
| | |
| | PLEASE PROVIDE A DETAILED SITE PLAN. |
| | |
| | |
| | |
| | 6) |
| | SHEET AC 1.00 - THERE IS A REFERENCE TO AN ELECRICAL |
| | SHEET FOR EMERGENCY LIGHTING. NO ELECTRICAL SHEET |
| | SUBMITTED. |
| | |
| | |
| | |
| | 7) |
| | THRE IS NO INDICATIONS OF A FIRE ALARM |
| | |
| | 16.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| | 16.3.4.1 GENERAL. DAY-CARE OCCUPANCIES, OTHER THAN |
| | DAY-CARE OCCUPANCIES HOUSED IN ONE ROOM HAVING AT LEAST |
| | ONE DOOR OPENING DIRECTLY TO THE OUTSIDE AT GRADE PLANE |
| | OR TO AN EXTERIOR EXIT ACCESS BALCONY IN ACCORDANCE |
| | WITH 7.5.3, SHALL BE PROVIDED WITH A FIRE ALARM SYSTEM |
| | IN ACCORDANCE WITH SECTION 9.6. |
| | 16.3.4.2 INITIATION. INITIATION OF THE REQUIRED FIRE |
| | ALARM SYSTEM SHALL BE BY MANUAL MEANS AND BY OPERATION |
| | OF ANY REQUIRED SMOKE DETECTORS AND REQUIRED SPRINKLER |
| | SYSTEMS. (SEE 16.3.4.5.) |
| | |
| | |
| | 8) |
| | THERE IS INSUFFICEINT INFORMATION SUBMITTED TO COMPLETE |
| | A COMPHRENSIVE FIRE PLAN REVIEW. PLEASE ENSURE THAT THE |
| | SUBMITTAL MEETS ALL THE REQUIRMENTS OF THE FLORIDA |
| | STATUTUE AND THE FLORIDA FIRE PREVENTION CODE FOR NEW |
| | DAY CARES. |
| | |
| | |
| | |
| | |
| | 9) |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | |
| | 10) |
| | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| | OF THE ABOVE. |
| | |
| | |
| | |
| | 11) |
| | THIS BUILDING DOES NOT MEET THE REQUIREMENTS FOR |
| | OCCUPANCY AS A DAY CARE AND SHALL NOT BE OCCUPIED UNTIL |
| | IT DOES AND HAS PASSED ALL APPLICABLE INSPECTIONS. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |