| 2017-04-06 11:28:43 | 410 DATURA STREET |
| | PERMIT #17031143 |
| | MASTER #16020194 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | IF ED SNIDER (PE #71374) IS TO BE THE SUCCESSOR FIRE |
| | PROTECTION ENGINEER OF RECORD THEN THE FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FROM THE MASTER PERMIT |
| | (#16020194) NEED TO REFLECT THIS CHANGE IN LIEU OF |
| | ATTEMPTING THIS CHANGE ON THE FIRE SPRINKLER SUB-PERMIT |
| | SHOP DRAWINGS (#17031143). |
| | |
| | SHEET FP1.0: PROVIDE LOCKING KNOX CAPS ON FIRE |
| | DEPARTMENT CONNECTION. |
| | |
| | SHEET FP3.0: THE SCHEDULE INDICATES THE FIRE PUMP |
| | HORSEPOWER TO BE 40 HP; HOWEVER, THE SPECIFICATIONS |
| | INDICATE 25 HP. PLEASE INDICATE THE CORRECT HP. |
| | |
| | SHEET FP6.6: NO SPRINKLER PROTECTION FOR PARKING GARAGE |
| | TENANT STORAGE. |
| | |
| | SHEET FP7.1B: THE SPRINKLERS LOCTED IN THE HIGH CEILING |
| | WILL NEED TO BE SUPPLIED FROM THE FIRST FLOOR |
| | SYSTEM/FLOW SWITCH; OTHERWISE A FIRE ON THE FIRST FLOOR |
| | IN THIS LOCATION WILL BE ALARMED TO THE SECOND FLOOR |
| | FLOW SWITCH AND COULD CREATE CONFUSION FOR RESPONDING |
| | FIREFIGHTERS. |
| | |
| | SHEET FP7.1C: THE SPRINKLERS LOCTED IN THE HIGH CEILING |
| | WILL NEED TO BE SUPPLIED FROM THE FIRST FLOOR |
| | SYSTEM/FLOW SWITCH; OTHERWISE A FIRE ON THE FIRST FLOOR |
| | IN THIS LOCATION WILL BE ALARMED TO THE SECOND FLOOR |
| | FLOW SWITCH AND COULD CREATE CONFUSION FOR RESPONDING |
| | FIREFIGHTERS. |
| | |
| | SHEET FP7.2A: THE SPRINKLERS LOCTED IN THE HIGH CEILING |
| | WILL NEED TO BE SUPPLIED FROM THE FIRST FLOOR |
| | SYSTEM/FLOW SWITCH; OTHERWISE A FIRE ON THE FIRST FLOOR |
| | IN THIS LOCATION WILL BE ALARMED TO THE THIRD FLOOR |
| | FLOW SWITCH AND COULD CREATE CONFUSION FOR RESPONDING |
| | FIREFIGHTERS. |
| | |
| | SHEET FP7.5D: HYDRAULIC DESIGN D (UNIT TYPE A1) |
| | SPRINKLER LAYOUT DOES NOT MATCH THE SPRINKLER LAYOUT |
| | FOR UNIT TYPE A1 AS SHOWN ON SHEET FP5.0. |
| | |
| | SHEET FP7.5D: DESIGN AREA D HYDRAULICALLY CALCULATES |
| | SPRINKLERS CLOSEST TO THE CROSSMAIN IN LIEU OF |
| | CALCULATING SPRINKLERS THAT ARE MORE REMOTE OR MORE |
| | HYDRAULICALLY DEMANDING. FOR EXAMPLE, RECESSED PENDENT |
| | (SIN R3516) IS INDICATED AS PROTECTING 20'X20' AND THE |
| | LISTING REQUIRES 20 GPM; HOWEVER, THE GREATEST FLOW IN |
| | THE CALCULATION IS ONLY 18 GPM. IF 4 SPRINKLERS ON THE |
| | REMOTE PORTION OF THE BRANCHLINE ARE CALCULATED, DOES |
| | THIS RESULT IN A GREATER PRESSURE DEMAND DUE TO THE |
| | FRICTION LOSS ASSOCIATED WITH THE 28 FEET OF 3/4" |
| | PIPING PLUS FITTINGS? |
| | |
| | SHEET FP8.0: STANDARD SPRAY SPRINKLERS IN THE LOUNGE |
| | ARE LOCATED MORE THAN 15 FEET APART. |
| | |
| | SHEET FP8.1 & 8.2: THE DRAWING SCALE IS INDICATED AS |
| | 1/8"=1'-0"; HOWEVER, THE ACTUAL SCALE IS 1/4"=1'-0". |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |