Plan Review Notes
Plan Review Notes For Permit 17031143
Permit Number 17031143
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-04-06 11:28:43410 DATURA STREET
 PERMIT #17031143
 MASTER #16020194
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 IF ED SNIDER (PE #71374) IS TO BE THE SUCCESSOR FIRE
 PROTECTION ENGINEER OF RECORD THEN THE FIRE PROTECTION
 CONSTRUCTION DOCUMENTS FROM THE MASTER PERMIT
 (#16020194) NEED TO REFLECT THIS CHANGE IN LIEU OF
 ATTEMPTING THIS CHANGE ON THE FIRE SPRINKLER SUB-PERMIT
 SHOP DRAWINGS (#17031143).
  
 SHEET FP1.0: PROVIDE LOCKING KNOX CAPS ON FIRE
 DEPARTMENT CONNECTION.
  
 SHEET FP3.0: THE SCHEDULE INDICATES THE FIRE PUMP
 HORSEPOWER TO BE 40 HP; HOWEVER, THE SPECIFICATIONS
 INDICATE 25 HP. PLEASE INDICATE THE CORRECT HP.
  
 SHEET FP6.6: NO SPRINKLER PROTECTION FOR PARKING GARAGE
 TENANT STORAGE.
  
 SHEET FP7.1B: THE SPRINKLERS LOCTED IN THE HIGH CEILING
 WILL NEED TO BE SUPPLIED FROM THE FIRST FLOOR
 SYSTEM/FLOW SWITCH; OTHERWISE A FIRE ON THE FIRST FLOOR
 IN THIS LOCATION WILL BE ALARMED TO THE SECOND FLOOR
 FLOW SWITCH AND COULD CREATE CONFUSION FOR RESPONDING
 FIREFIGHTERS.
  
 SHEET FP7.1C: THE SPRINKLERS LOCTED IN THE HIGH CEILING
 WILL NEED TO BE SUPPLIED FROM THE FIRST FLOOR
 SYSTEM/FLOW SWITCH; OTHERWISE A FIRE ON THE FIRST FLOOR
 IN THIS LOCATION WILL BE ALARMED TO THE SECOND FLOOR
 FLOW SWITCH AND COULD CREATE CONFUSION FOR RESPONDING
 FIREFIGHTERS.
  
 SHEET FP7.2A: THE SPRINKLERS LOCTED IN THE HIGH CEILING
 WILL NEED TO BE SUPPLIED FROM THE FIRST FLOOR
 SYSTEM/FLOW SWITCH; OTHERWISE A FIRE ON THE FIRST FLOOR
 IN THIS LOCATION WILL BE ALARMED TO THE THIRD FLOOR
 FLOW SWITCH AND COULD CREATE CONFUSION FOR RESPONDING
 FIREFIGHTERS.
  
 SHEET FP7.5D: HYDRAULIC DESIGN D (UNIT TYPE A1)
 SPRINKLER LAYOUT DOES NOT MATCH THE SPRINKLER LAYOUT
 FOR UNIT TYPE A1 AS SHOWN ON SHEET FP5.0.
  
 SHEET FP7.5D: DESIGN AREA D HYDRAULICALLY CALCULATES
 SPRINKLERS CLOSEST TO THE CROSSMAIN IN LIEU OF
 CALCULATING SPRINKLERS THAT ARE MORE REMOTE OR MORE
 HYDRAULICALLY DEMANDING. FOR EXAMPLE, RECESSED PENDENT
 (SIN R3516) IS INDICATED AS PROTECTING 20'X20' AND THE
 LISTING REQUIRES 20 GPM; HOWEVER, THE GREATEST FLOW IN
 THE CALCULATION IS ONLY 18 GPM. IF 4 SPRINKLERS ON THE
 REMOTE PORTION OF THE BRANCHLINE ARE CALCULATED, DOES
 THIS RESULT IN A GREATER PRESSURE DEMAND DUE TO THE
 FRICTION LOSS ASSOCIATED WITH THE 28 FEET OF 3/4"
 PIPING PLUS FITTINGS?
  
 SHEET FP8.0: STANDARD SPRAY SPRINKLERS IN THE LOUNGE
 ARE LOCATED MORE THAN 15 FEET APART.
  
 SHEET FP8.1 & 8.2: THE DRAWING SCALE IS INDICATED AS
 1/8"=1'-0"; HOWEVER, THE ACTUAL SCALE IS 1/4"=1'-0".
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  