| 2017-05-05 13:10:21 | 2ND REVIEW COMMENTS |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. |
| | |
| | FAILURE TO FOLLOW THESE PROVISO COMMENTS WILL RESULT IN |
| | A FAILED FIRE INSPECTION. |
| | |
| | |
| | 1) |
| | SHEET 1.1 - THERE IS NO INDICATION OF A FIRE CODE |
| | REFERENCE AND/OR COMPLIANCE. |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | |
| | PLEASE ENSURE ALL WORK IS DONE IN COMPLIANCE WITH THE |
| | ABOVE NOTED CODE. |
| | |
| | |
| | |
| | |
| | 2) |
| | SHEET 1.1 - THERE ARE INDICATIONS OF WALLS THAT ARE |
| | BEING REMOVED AND NEW WALLS INSTALLED (OR A RAISED |
| | CEILING). |
| | |
| | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR |
| | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND |
| | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY |
| | CERTIFIED LIFE SAFETY CONTRACTORS. |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | PLEASE ENSURE COMPLIANCE WITH: |
| | |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | |
| | |