| 2017-04-05 08:08:10 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17031134 |
| | ADD: 529 S. FLAGLER DR. SUITE # 6F |
| | CONT: ALBRIGHT CONSTRUCTION |
| | TEL: 561-547-7433 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: WED. APRIL 05/ 2017 |
| | ACTION: DENIED |
| | |
| | 1) ALBRIGHT LETTER FOR THE SCOPE OF WORK ON PAGE NUMBER |
| | 2 UNDER THE HEADING GENERAL LIST THE REPLACEMENT OF |
| | EXTERIOR WINDOWS AND DOORS. THE COVER SHEET PROVIDES |
| | THE WIND DESIGN CRITERIA AND SHEET # 1 SHOWS THE |
| | OPENINGS IDENTIFIED AS OPENINGS 1-5. THE COVER SHEET |
| | UNDER THE HEADING WIND DESIGN DATA STATES THAT THE WIND |
| | PRESSURES ARE TO BE CALCULATED BY DANIEL J. MOSS P. E. |
| | SIGNED & SEALED LETTER TO BE STAPLED TO PLAN SETS. IN |
| | THIS SUBMITTAL NO SUCH LETTER WAS SUBMITTED IN THE |
| | PERMIT PACKAGE DOCUMENTS. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| | HEIGHT AND EXPOSURE. |
| | |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 2) COMPONENTS & CLADDING. 2010/ 2014 FBC-B 1609.1.2 |
| | PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS & |
| | CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS, |
| | ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/ |
| | 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS ,MULLIONS. |
| | (B) WINDOWS & MULLIONS. |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS. |
| | |
| | 3) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS |
| | WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR |
| | SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS, |
| | SHOP DRAWINGS ETC.. |
| | |
| | 4) THE PLANS SHEET # 1 INDICATES THE USE OF SUPER SAM |
| | 125 FLOOR UNDERLAYMENT/ INSULATION. THE DOCUMENT |
| | SUBMITTED IS A SALES BROCHURE NOT THE ACTUAL TEST DATA. |
| | NOTE THE TEST SHOULD SHOW IT IS FOR A 6 INCH CONCRETE |
| | SLAB AND NO DROP CEILING. THE SOUND TEST ALSO NEEDS TO |
| | DECLARE IF THE FINISH FLOOR MATERIAL IS MARBLE, TILE |
| | AND OR WOOD, OR WOOD LAMINATE, MUST BE SPECIFIC TO THE |
| | FINISH FLOOR MATERIAL. |
| | |
| | BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| | 2014) |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | 4A) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 4B) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 4C) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 5) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |