| Plan Review Notes For Permit 17031108 |
| Permit Number |
17031108 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-30 19:20:33 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE LETTER FROM THE DURAPAX SALES MANAGER IS NOT | | | ACCEPTABLE. THE LETTER CALLS FOR INSTALLING A TORCH | | | APPLIED PLY OF DURAPAX SMOOTH POLYESTER APP DIRECTLY TO | | | THE PRIMED CONCRETE DECK. THE APPROVED ASSEMBLY THAT | | | YOU PROPOSE TO USE FROM NOA NO.13-1022.08, SYSTEM TYPE | | | A, REQUIRES ALL LAYERS OF INSULATION TO BE HOT MOPPED | | | DIRECTLY TO THE PRIMED CONCRETE DECK AND THE ROOF | | | MEMBRANES ARE THEN HOT MOPPED OVER THE INSULATION. THE | | | INSTALLATION CAN NOT DEVIATE FROM THE TESTED AND | | | APPROVED ASSEMBLY. FBC 1504.1 |
|