2017-04-04 08:30:41FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70 2011 EDITION
  
 FBC-EC405.2.4 EXTERIOR LIGHTING CONTROLS. LIGHTING NOT
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY EITHER A COMBINATION OF A PHOTOSENSOR AND
 A TIME SWITCH, OR AN ASTRONOMICAL TIME SWITCH. LIGHTING
 DESIGNATED FOR DUSK-TO-DAWN OPERATION SHALL BE
 CONTROLLED BY AN ASTRONOMICAL TIME SWITCH OR
 PHOTOSENSOR. ALL TIME SWITCHES SHALL BE CAPABLE OF
 RETAINING PROGRAMMING AND THE TIME SETTING DURING LOSS
 OF POWER FOR A PERIOD OF AT LEAST 10 HOURS.
  
 C405.6 EXTERIOR LIGHTING (MANDATORY). WHERE THE POWER
 FOR EXTERIOR LIGHTING IS SUPPLIED THROUGH THE ENERGY
 SERVICE TO THE BUILDING, ALL EXTERIOR LIGHTING, OTHER
 THAN LOW-VOLTAGE LANDSCAPE LIGHTING, SHALL COMPLY WITH
 SECTIONS C405.6.1 AND C405.6.2.
  
 C405.6.2 EXTERIOR BUILDING LIGHTING POWER. THE TOTAL
 EXTERIOR LIGHTING POWER ALLOWANCE FOR ALL EXTERIOR
 BUILDING APPLICATIONS IS THE SUM OF THE BASE SITE
 ALLOWANCE PLUS THE INDIVIDUAL ALLOWANCES FOR AREAS THAT
 ARE TO BE ILLUMINATED AND ARE PERMITTED IN TABLE
 C405.6.2(2) FOR THE APPLICABLE LIGHTING ZONE. TRADEOFFS
 ARE ALLOWED ONLY AMONG EXTERIOR LIGHTING APPLICATIONS
 LISTED IN TABLE C405.6.2(2), TRADABLE SURFACES SECTION.
 THE LIGHTING ZONE FOR THE BUILDING EXTERIOR IS
 DETERMINED FROM TABLE C405.6.2(1) UNLESS OTHERWISE
 SPECIFIED BY THE LOCAL JURISDICTION. EXTERIOR LIGHTING
 FOR ALL APPLICATIONS (EXCEPT THOSE INCLUDED IN THE
 EXCEPTIONS TO SECTION C405.6.2) SHALL COMPLY WITH THE
 REQUIREMENTS OF SECTION C405.6.1.
  
 PROVIDE CUT SHEETS FOR POLES AND FIXTURES, TIME CLOCK
 AND/OR PHOTOCELL.
  
  