2017-05-22 07:59:40****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 REVIEW #2 (FIRST RESUBMITTAL)
  
 1. THE PERMIT FOR THE SHELL IS NOT ISSUED. THIS PERMIT
 CANNOT BE ISSUED UNTIL THE SHELL IS ISSUED (17021163).
 THIS PERMIT WILL BE ISSUED AT RISK; RESPONSIBILITY FOR
 A CODE COMPLIANT PROJECT IS ON APPLICANTS FOR THE TWO
 PERMITS AND THEY ARE TO WORK TOGETHER TO RESOLVE ANY
 ISSUES.
  
 2ND REVIEW, A LETTER OF ACKNOWLEDGEMENT SIGNED BY BOTH
 CONTRACTORS WILL BE REQUIRED PRIOR TO PERMIT ISSUANCE.
 SHELL IS NOT YET ISSUED AT THE TIME OF THIS REVIEW.
  
 2. A CURSORY REVIEW OF THE (ENERGY CALC) INPUT DATA
 REPORT WAS DONE. CLARIFY THE FOLLOWING:
 WALLS - 3 SHOWN, IT APPEARS THAT THE FOURTH WALL IS NOT
 IN THE REPORT
 WALLS OR WINDOWS - SOME WINDOWS ON THE PLAN ARE TO HAVE
 DRYWALL INSTALLED ON THE INSIDE. CLARIFY HOW THIS IS
 HANDLED ON THE PLAN; ARE THESE AREAS ACCOUNTED FOR AS
 WINDOWS?
 DOORS - NONE SHOWN; ARE ALL EXTERIOR DOORS GLAZED? ARE
 THEY INCLUDED IN THE WINDOWS OR FENESTRATION NUMBERS?
 FENESTRATION - 1 PANE SHOWN; CLARIFY WHAT THIS ITEM IS.
 ROOF - R19 INSULATION SPECIFIED AND TOTAL R VALUE OF
 22.6 - SEE NOTE 7 SHEET A4.0 FOR SHELL PERMIT; NOTE
 SPECIFIES INSULATION TO ACHIEVE R19, PLEASE CORRELATE
 (EITHER REVISE THE INPUT DATA REPORT AND ENERGY CALC TO
 SPEC TOTAL R19 FOR ROOF, OR REVISE SHELL PERMIT TO
 SPECIFY R19 BOARD).
  
 3. REVISE PLAN TO SHOW INFORMATION REGARDING AMOUNT OF
 RADIATION AND DESIGN OF WALLS TO SHOW COMPLIANCE WITH
 ALL REQUIREMENTS OF FBC B 465, FAC 64E-5, FS 404 (AS
 APPLICABLE). NOT ENOUGH INFORMATION PROVIDED TO
 DETERMINE CODE COMPLIANCE.
  
 2ND REVIEW, INFORMATION FROM DOH WAS PROVIDED. REVISE
 PLAN TO STATE AMOUNT OF RADIATION PROPOSED ("<200 KVP"
 IS ACCEPTABLE IF THAT IS THE CASE) AND REVISE PLAN TO
 PROVIDE A DETAIL FOR THE LEAD LINED WALLS, OR REVISE W3
 AND W5 (SHEET A1) TO CLARIFY LEAD INSTALLATION
 REQUIREMENTS. DETAILS STATE "LEAD @ X-RAY ROOM" BUT
 DOES NOT SPECIFY LEAD THICKNESS OR HEIGHT.
  
 NEW COMMENT:
  
 THE PAGES WHICH WERE REVISED TO ADDRESS COMMENTS FROM
 FIRST REVIEW ARE NOT SEALED BY THE ARCHITECT. DOCUMENTS
 PREPARED BY AN ARCHITECT AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED, SEALED, DATED ORIGINALS FS481.
  
 FOR INSTANCE, SEE A2, I2, I3, CHECK ALL.
  
  
  