Plan Review Notes
Plan Review Notes For Permit 17031082
Permit Number 17031082
Review Stop P
Sequence Number 1
Notes
Date Text
2017-04-10 12:19:401ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHT. A-2 GRAB BARS SHALL BE INSTALLED IN A
 HORIZONTAL POSITION, 33 INCHES (840 MM) MINIMUM AND 36
 INCHES (915 MM) MAXIMUM ABOVE THE FINISH FLOOR MEASURED
 TO THE TOP OF THE GRIPPING SURFACE. PER FBC ACC 609.4
 2. SHT. A-2 THE SIDE WALL GRAB BAR SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305 MM)
 MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES
 (1370 MM) MINIMUM FROM THE REAR WALL. PER FBC ACC
 604.5.1
 3. SHT. A-2 TOILET PAPER DISPENSERS SHALL COMPLY WITH
 309.4 AND SHALL BE 7 INCHES (180 MM) MINIMUM AND 9
 INCHES (230 MM) MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. THE OUTLET
 OF THE DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM
 AND 48 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR
 AND SHALL NOT BE LOCATED BEHIND GRAB BARS. PER FBC ACC
 604.7
 4. SHT. A-2 THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT. SEATS SHALL NOT BE SPRUNG TO RETURN TO A LIFTED
 POSITION. PER FBC ACC 604.4
 5. SHT. A-2 THE WATER CLOSET SHALL BE POSITIONED WITH A
 WALL OR PARTITION TO THE REAR AND TO ONE SIDE. THE
 CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES (405
 MM) MINIMUM TO 18 INCHES (455 MM) MAXIMUM FROM THE SIDE
 WALL OR PARTITION. PER FBC ACC 604.2
 6. SHT. A-2 SHOW CLEAR FLOOR SPACE FOR DRINKING
 FOUNTAIN AND BREAK ROOM SINK. PER WPB AMEND TO FBC
 107.2.1
 7. AT LEAST ONE OF THE PROCEDURE ROOM SINKS SHALL
 COMPLY WITH FBC ACC 606 PER FBC ACC 212.3
 8. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
 9. WATER HAMMER ARRESTERS ARE REQUIRED FOR WASHING
 MACHINE AND ICE MAKER. PER FBC PL 604.9
 10. A BACK FLOW IS REQUIRED FOR REF ICE MACHINE. PER
 FBC PL 608.3
  
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  