| Plan Review Notes For Permit 17031082 |
| Permit Number |
17031082 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-31 16:14:29 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | NEED FAULT CURRENT CALCULATION AND LAELING AT SERVICE | | | PER 110.24(A,B) | | | | | | WIRE SIZE FROM MAIN DISCONNECT TO THE GUTTER 215.5 | | | | | | PLEASE INDICATE ON PLANS WHICH ROOMS SHALL BE WIRED PER | | | 517.13 | | | | | | PLEASE INDICATE THE LIGHTING CONTROL PER FBC ENERGY | | | C405.2.2.2 | | | | | | PLEASE INDICATE THE RECEPTACLE CONTROL REQUIRED BY FBC | | | C401.2 AND ASHREA 8.4.2 | | | | | | | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | BN1165, BU1753, PX163 | | | 561-805-6713 | | | |
|