| Plan Review Notes For Permit 17031082 |
| Permit Number |
17031082 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-31 09:40:29 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | | | | 1. THE PERMIT FOR THE SHELL IS NOT ISSUED. THIS PERMIT | | | CANNOT BE ISSUED UNTIL THE SHELL IS ISSUED (17021163). | | | THIS PERMIT WILL BE ISSUED AT RISK; RESPONSIBILITY FOR | | | A CODE COMPLIANT PROJECT IS ON APPLICANTS FOR THE TWO | | | PERMITS AND THEY ARE TO WORK TOGETHER TO RESOLVE ANY | | | ISSUES. | | | | | | 2. I WAS UNABLE TO LOCATE THE INPUT DATA REPORT FOR THE | | | ENERGY CALCS, FBC 107. PRIOR TO SUBMITTAL, CONFIRM THAT | | | IT IS COMPLETE (WINDOWS, DOORS, ETC.) AND ACCURATE. | | | | | | 3. REVISE PLAN TO SHOW INFORMATION REGARDING AMOUNT OF | | | RADIATION AND DESIGN OF WALLS TO SHOW COMPLIANCE WITH | | | ALL REQUIREMENTS OF FBC B 465, FAC 64E-5, FS 404 (AS | | | APPLICABLE). NOT ENOUGH INFORMATION PROVIDED TO | | | DETERMINE CODE COMPLIANCE. | | | | | | 4. A2 WATER CLOSET MINIMUM DISTANCE TO WALL IS 18"; | | | REVISE TO COMPLY WITH FBC A 402.2, RANGE IS 16"MIN, 18" | | | MAX. MORE THAN ONE NOTE AFFECTED; REVISE ALL. | | | | | | 5. FBC A 603.2 TURNING SPACE (FBC A 304) REQUIRED. | | | RECTANGLES ARE SHOWN; A CIRCLE OR A T TURNING SPACE IS | | | REQUIRED; REVISE ACCORDINGLY. | | | |
|