Plan Review Notes
Plan Review Notes For Permit 17031082
Permit Number 17031082
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-31 09:40:29****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. THE PERMIT FOR THE SHELL IS NOT ISSUED. THIS PERMIT
 CANNOT BE ISSUED UNTIL THE SHELL IS ISSUED (17021163).
 THIS PERMIT WILL BE ISSUED AT RISK; RESPONSIBILITY FOR
 A CODE COMPLIANT PROJECT IS ON APPLICANTS FOR THE TWO
 PERMITS AND THEY ARE TO WORK TOGETHER TO RESOLVE ANY
 ISSUES.
  
 2. I WAS UNABLE TO LOCATE THE INPUT DATA REPORT FOR THE
 ENERGY CALCS, FBC 107. PRIOR TO SUBMITTAL, CONFIRM THAT
 IT IS COMPLETE (WINDOWS, DOORS, ETC.) AND ACCURATE.
  
 3. REVISE PLAN TO SHOW INFORMATION REGARDING AMOUNT OF
 RADIATION AND DESIGN OF WALLS TO SHOW COMPLIANCE WITH
 ALL REQUIREMENTS OF FBC B 465, FAC 64E-5, FS 404 (AS
 APPLICABLE). NOT ENOUGH INFORMATION PROVIDED TO
 DETERMINE CODE COMPLIANCE.
  
 4. A2 WATER CLOSET MINIMUM DISTANCE TO WALL IS 18";
 REVISE TO COMPLY WITH FBC A 402.2, RANGE IS 16"MIN, 18"
 MAX. MORE THAN ONE NOTE AFFECTED; REVISE ALL.
  
 5. FBC A 603.2 TURNING SPACE (FBC A 304) REQUIRED.
 RECTANGLES ARE SHOWN; A CIRCLE OR A T TURNING SPACE IS
 REQUIRED; REVISE ACCORDINGLY.
  