| 2017-03-30 15:22:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) |
| | SHEET C 1 - THERE IS NO REFERNENCE TO THE FLORIDA FIRE |
| | PREVENTION CODE OR ANY OTHER FIRE CODE. |
| | |
| | PLEASE PROVIDE A NOTE: |
| | |
| | THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| | 5TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| | THE 2012 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| | APPLICABLE CODES OR STANDARDS. |
| | FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| | OF NFPA 13, 2010 EDITION. |
| | FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 72, 2010 EDITION. |
| | CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| | NFPA 241, 2009 EDITION. |
| | |
| | |
| | |
| | 2) |
| | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR |
| | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND |
| | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY |
| | CERTIFIED LIFE SAFETY CONTRACTORS. |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | PLEASE PROVIDE AN APPLICABLE NOTE. |
| | |
| | |
| | |
| | 3) |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | |
| | |
| | 4) |
| | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| | OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |