2017-03-30 11:58:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. C1 SITE DATA DECLARES THIS AS R1; SEE FBC B 310.
 THIS BUILDING WAS PERMITTED AS CONDOMINIUMS. IF A
 CHANGE OF OCCUPANCY IS PROPOSED (FROM R2 TO R1), REVISE
 PLAN TO SHOW COMPLIANCE WITH ALL REQUIERMENTS OF FBC EB
 CHAPTER 10, CHANGE OF OCCUPANCY.
  
 2. SPEC SHEET FOR "ISO-STEP FLOOR UNDERLAYMENT" WAS
 SUBMITTED. PROVIDE THE FOLLOWING TEST REPORTS:
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 3. C1, TOP LEFT, PAGE DID NOT PRINT PROPERLY. RE-PRINT
 AND CONFIRM THAT ALL TEXT PRINTS LEGIBLY.
  
 4. VALUE IS TOO LOW. VALUE IS TO INCLUDE LABOR,
 MATERIALS, OVERHEAD, PROFIT, EVEN IF PROVIDED BY
 OTHERS, FBC 109.
  
 5. C1, SITE DATA, CONTRUCTION TYPE HAS A SYMBOL WHICH
 IS NOT CLEAR, AND STATES "APARTMENT". THIS IS NOT A
 BUILDING TYPE, SEE FBC CHAPTER 6 AND REVISE.
  
 6. COMPLIANCE WITH FBC A FAIR HOUSING NOT CLEAR.
 CONSTRUCTED IN 2006, THIS IS CONSIDERED A COVERED UNIT.
 REVISE PLAN TO SHOW COMPLIANCE, FBC 107.
  
 YOU MAY FIND THE FOLLOWING WEBSITE HELPFUL, FREQUENTLY
 ASKED QUESTION #8:
  
 HTTP://WWW.FAIRHOUSINGFIRST.ORG/FAQ/VIEW_ALL.HTML
  
 THE DOJ/HUD JOINT STATEMENT, ADDENDUM TO FAIR HOUSING
 ACT, STATES:
  
 "DO THE FAIR HOUSING ACT'S DESIGN AND CONSTRUCTION
 REQUIREMENTS APPLY TO ALTERATION OR RENOVATION OF
 PROPERTIES?
 ALTERATIONS, REHABILITATION OR REPAIR OF COVERED
 MULTIFAMILY DWELLINGS ARE NOT COVERED BECAUSE THE ACT'S
 DESIGN AND CONSTRUCTION REQUIREMENTS ONLY APPLY TO NEW
 CONSTRUCTION OF BUILDINGS BUILT FOR FIRST OCCUPANCY
 AFTER MARCH 13, 1991. HOWEVER, A COVERED MULTIFAMILY
 DWELLING THAT HAS BEEN CONSTRUCTED TO COMPLY WITH THE
 LAW CANNOT LATER BE ALTERED TO MAKE IT NON-COMPLIANT
 WITH THE LAW."
  
 7. DETAIL 1-A1 SHOWS WOOD WALL FRAMING. FBC B 603,
 REVISE PLAN TO SHOW COMPLIANCE. BUILDING TYPE WAS NOT
 PROVIDED, BUT AS A HIGH RISE IT IS LIKELY A NON
 COMBUSTIBLE BUILDING.
  
 8. FBC 107, FBC B 1207, REVISE PLAN TO INCLUDE FLOOR
 SLAB THICKNESS, OR PROVIDE A COPY OF THE PAGE FROM THIS
 BUILDING'S ORIGINAL CONSTRUCTION WHICH SHOWS THIS
 INFORMATION. SPEC SHEETS PROVIDE STC AND IIC
 INFORMATION FOR AN 8" SLAB. SLAB INFORMATION IS
 REQUIRED TO PROPOSE AN UNDERLAYMENT PRODUCT TESTED ON
 AN 8" SLAB. OTHERWISE, TEST REPORTS FOR A 6" SLAB IS
 REQUIRED (MOST CONSERVATIVE CONDITION).
  