| 2017-04-12 09:39:53 | 1ST REVIEW: FBC 2014 5TH ED. RESIDENTIAL |
| | 1ST REVIEW FBC 2014 EXISTING BUILDING |
| | |
| | RESULT FAIL |
| | |
| | THIS APPLICATION IS TO RESOLVE WORK DONE WITHOUT A |
| | PERMIT AS DESCRIBED IN CE16060098. NO ELECTRICAL |
| | INFORMATION HAS BEEN PROVIDED. PLEASE HAVE THE PROPERTY |
| | INSPECTED BY A LICENSED ELECTRICIAN AND COORDINATE THE |
| | ELECTRICIAN TO APPIY FOR AN ELECTRICAL PERMIT AS A SUB |
| | PERMIT TO THIS APPLICATION. THE ELECTRICIAN SHOULD |
| | INSPECT THE PROPERTY INCLUDING DESTRUCTIVE INSPECTION |
| | IF NEEDED AND BE PREPARED TO PROVIDE A REPORT |
| | SPECIFYING CORRECTIONS NEEDED AND FURTHER BE PREPARED |
| | TO CERTIFY COMPLIANCE WITH APPLICABLE REQUIREMENTS. |
| | |
| | IN ADDITION TO GENERAL CONFORMANCE TO THE REQUIREMENTS |
| | OF APPLICABLE CODE, THE FOLLOWING MAY BE REQUIRED IF |
| | NOT CURRENTLY PROVIDED. |
| | |
| | FBC- 107.3.5.3 SMOKE DETECTORS PURSUANT TO FBC-R |
| | 314.3.1 AS REQUIRED FOR NEW DWELLINGS. |
| | |
| | FBCRE 3901.2.1 SPACING. |
| | RECEPTACLES SHALL BE INSTALLED SO THAT NO POINT |
| | MEASURED HORIZONTALLY ALONG THE FLOOR LINE OF ANY WALL |
| | SPACE IS MORE THAN 6 FEET (1829 MM), FROM A RECEPTACLE |
| | OUTLET. |
| | |
| | FBCRE 3703.2 KITCHEN AND DINING AREA RECEPTACLES. |
| | A MINIMUM OF TWO 20-AMPERE-RATED BRANCH CIRCUITS SHALL |
| | BE PROVIDED TO SERVE ALL WALL AND FLOOR RECEPTACLE |
| | OUTLETS LOCATED IN THE KITCHEN, PANTRY, BREAKFAST AREA, |
| | DINING AREA OR SIMILAR AREA OF A DWELLING. THE KITCHEN |
| | COUNTERTOP RECEPTACLES SHALL BE SERVED BY A MINIMUM OF |
| | TWO 20-AMPERE-RATED BRANCH CIRCUITS, EITHER OR BOTH OF |
| | WHICH SHALL ALSO BE PERMITTED TO SUPPLY OTHER |
| | RECEPTACLE OUTLETS IN THE SAME KITCHEN, PANTRY, |
| | BREAKFAST AND DINING AREA INCLUDING RECEPTACLE OUTLETS |
| | FOR REFRIGERATION APPLIANCES. |
| | |
| | FBCE 3902.3 OUTDOOR RECEPTACLES. |
| | ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | RECEPTACLES INSTALLED OUTDOORS SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | |
| | FBCRE 3902.1 BATHROOM RECEPTACLES. |
| | ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | RECEPTACLES INSTALLED IN BATHROOMS SHALL HAVE |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. |
| | |
| | FBCE 3902.6 KITCHEN RECEPTACLES. |
| | ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | RECEPTACLES THAT SERVE COUNTERTOP SURFACES SHALL HAVE |
| | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION FOR |
| | PERSONNEL. |
| | |
| | FBCE 3902.7 SINK RECEPTACLES. |
| | ALL 125-VOLT, SINGLE-PHASE, 15- AND 20-AMPERE |
| | RECEPTACLES THAT ARE LOCATED WITHIN 6 FEET (1829 MM) OF |
| | THE OUTSIDE EDGE OF A SINK THAT IS LOCATED IN AN AREA |
| | OTHER THAN A KITCHEN, SHALL HAVE GROUND-FAULT |
| | CIRCUIT-INTERRUPTER PROTECTION FOR PERSONNEL. |
| | RECEPTACLE OUTLETS SHALL NOT BE INSTALLED IN A FACE-UP |
| | POSITION IN THE WORK SURFACES OR COUNTERTOPS. |
| | |
| | FBCRE 3902.12 ARC-FAULT CIRCUIT-INTERRUPTER PROTECTION. |
| | ALL BRANCH CIRCUITS THAT SUPPLY 120-VOLT, SINGLE-PHASE, |
| | 15- AND 20-AMPERE OUTLETS INSTALLED IN FAMILY ROOMS, |
| | DINING ROOMS, LIVING ROOMS, PARLORS, LIBRARIES, DENS, |
| | BEDROOMS, SUNROOMS, RECREATIONS ROOMS, CLOSETS, |
| | HALLWAYS AND SIMILAR ROOMS OR AREAS SHALL BE PROTECTED |
| | BY A COMBINATION TYPE ARC-FAULT CIRCUIT INTERRUPTER |
| | INSTALLED TO PROVIDE PROTECTION OF THE BRANCH CIRCUIT. |
| | |
| | FBCRE 4002.14 TAMPER-RESISTANT RECEPTACLES. |
| | IN AREAS SPECIFIED IN SECTION E3901.1, 125-VOLT, 15- |
| | AND 20-AMPERE RECEPTACLES SHALL BE LISTED |
| | TAMPER-RESISTANT RECEPTACLES. |
| | |
| | PLEASE BE ADVISED THE INSPECTOR MAY REQUIRE PREVIOUSLY |
| | COMPLETED WORK TO BE MADE ACCESSIBLE AND OPEN FOR |
| | INSPECTION OR REQUIRE ADDITIONAL DOCUMENTATION FOR ALL |
| | CONCEALED WORK PREVIOUSLY COMPLETED PURSUANT TO FBC 110 |
| | & FBC 117. |
| | FBC 110.1 GENERAL. CONSTRUCTION OR WORK FOR WHICH A |
| | PERMIT IS REQUIRED SHALL BE SUBJECT TO INSPECTION BY |
| | THE BUILDING OFFICIAL AND SUCH CONSTRUCTION OR WORK |
| | SHALL REMAIN ACCESSIBLE AND EXPOSED FOR INSPECTION |
| | PURPOSES UNTIL APPROVED. |
| | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| | |
| | |