| Plan Review Notes For Permit 17030975 |
| Permit Number |
17030975 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-28 06:23:53 | 1) SUBMIT 2 COPIES OF THE MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS FOR THIS SYSTEM. WPB AMEND. TO FBC SEC. | | | 107.2.1, 2014 FBC-PLUMBING SEC.303.2. | | | 2) ALL PLASTIC PIPE, FITTINGS AND COMPONENTS SHALL | | | COMPLY WITH NSF 14. 2014 FBC-PLUMBING SEC.303.3. | | | 3) ALL PLUMBING PRODUCTS AND MATERIALS SHALL BE LISTED | | | BYA THIRD-PARTY CEERTIFICATION AGENCY AS COMPLYING WITH | | | THE REFERENCED STANDARDS. PRODUCTS AND MATERIALS SHALL | | | BE IDENTIFIED IN ACCORDANCE WITH FPC SEC. 303.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | |
|