| 2017-04-12 15:19:59 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET SK 1 - THERE IS AN INDICATION OF A FUEL TANK | | | WHILE SHEET E 1 COMMENT NOTE # 5 INDICATES NATURAL GAS. | | | | | | CONFLICT, PLEASE CORRECT OR CLARIFY. | | | | | | | | | | | | 2) INFORMATION REQUEST - WILL THIS GENERATOR SUPPLY | | | BACK-UP POWER TO A FIRE ALARM OR OTHER LIFE SAFETY | | | SYSTEM? | | | | | | PROVIDE APPLICABLE NOTE | | | | | | | | | | | | 3) IF YES TO # 2, PLEASE ENSURE COMPLIANCE WITH NFPA | | | 110 STANDARD FOR EMERGENCY AND STANDBY POWER SYSTEMS | | | 2010 EDITION | | | | | | PROVIDE APPLICABLE NOTE | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|