| Plan Review Notes For Permit 17030959 |
| Permit Number |
17030959 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-14 13:29:55 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. TOILET AND SHOWER DOWN STAIRS ARE NOT VENTED SHOULD | | | BE VENTED TOGETHER WITH LAV. PER FBC PL 901.2.1\ | | | | | | 2. CLEAN OUTS ARE REQUIRED AT THE BASE OF SOIL STACKS. | | | FBC PL 708.3.4 | | | | | | 3. ONE VENT SHALL TERMINATE OUTDOORS. PER FBC PL 904.3 | | | | | | 4. PROVIDE MANUFACTURES SPES FOR TANKLESS WATER HEATER. | | | WPB AMEND TO FBC 107.2.1 | | | | | | | | | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT | | | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL | | | COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|