| Plan Review Notes For Permit 17030959 |
| Permit Number |
17030959 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-05-10 09:26:09 | PLAN DENIED | | | 1) PROVIDE TYPE OF EQUIPMENT ON EQUIPMENT SCHEDULE | | | PER SECTION 107 FBC | | | 2) PROVIDE CONDENSER TIE DOWN DETAIL. PER SECTION | | | 301.15 WIND FBC (M) 2014 | | | 3) MECHANICAL NOTE # 1 REFERS TO 2010 CODES. | | | WE ARE IN 2014 CODES. | | | 4) MECHANICAL NOTE # 5 STATES FLEX DUCT SHALL | | | BE R-6. REFER TO SECTION R403.2.1 FLORIDA ENERGY | | | CODE 2014 FLEX DUCT IN ATTIC SHALL BE A | | | MINIMUM OF R-8. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | OFFICE 561-805-6732 | | | FAX 561-805-6676 |
|