2017-05-10 09:26:09PLAN DENIED
 1) PROVIDE TYPE OF EQUIPMENT ON EQUIPMENT SCHEDULE
 PER SECTION 107 FBC
 2) PROVIDE CONDENSER TIE DOWN DETAIL. PER SECTION
 301.15 WIND FBC (M) 2014
 3) MECHANICAL NOTE # 1 REFERS TO 2010 CODES.
 WE ARE IN 2014 CODES.
 4) MECHANICAL NOTE # 5 STATES FLEX DUCT SHALL
 BE R-6. REFER TO SECTION R403.2.1 FLORIDA ENERGY
 CODE 2014 FLEX DUCT IN ATTIC SHALL BE A
 MINIMUM OF R-8.
  