| Plan Review Notes For Permit 17030959 |
| Permit Number |
17030959 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-04 11:20:40 | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE 2014 5TH ED. RESIDENTIAL | | | NFPA 70 2011 EDITION | | | | | | LOAD CALCULATION FOR PANEL "B" SHOWS 68 AMPERS WIRE | | | FROM MAIN IS ONLY #6, SOME OF THE NOTATIONS SHOW 100A | | | PANEL AND SOME SHOW 60A | | | PLEASE CLARIFY | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | BN1165, BU1753, PX163 | | | 561-805-6713 | | | | | | |
|