| Plan Review Notes For Permit 17030929 |
| Permit Number |
17030929 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-27 15:48:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) | | | THE SUBMITTED APPLICATION INDICATES AS-BUILT FIRE | | | SPRINKLER PLANS AND THE SUBMITTED PLAN SHEET INDICATES | | | AS BUILT; HOWEVER, THE SUBMITTED PLAN SHEET(S) DOES NOT | | | (DO NOT) INDICATE ANY CLOUD REVISIONS, CALL OUTS AND/OR | | | NOTES INDICATING WHAT AREAS, DEVICES, HEADS, PIPING, | | | ETC IS AS-BUILT OR REVISED FROM THE MASTER PERMIT. | | | | | | PER NFPA 1 | | | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | | | PLEASE CLEARLY INDICATE THE EACH AREA OR PIECE OF | | | EQUIPMENT REVISED/AS-BUILT ON THE PLAN SHEETS. | | | | | | | | | | | | 2) | | | THE SUBMITTED SHEETS WERE NOT BOUND TOGETHER OR | | | ORGAINZED SO THEY CAN NOT SEPARATE. | | | | | | PLEASE BIND AND/OR STAPLE YOUR SUBMITTED PLAN SHEETS | | | INTO ORGANIZED SETS. | | | | | | | | | | | | 3) | | | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION | | | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. | | | | | | | | | | | | 4) | | | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL | | | OF THE ABOVE. | | | | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|